EATON - MOELLER DB1-127D0FN-N2CC DB1-127D0FN-N2CC 197195 EATON ELECTRIC Cool Plate Frequency Converter Ent: 1 x 230V Salt: 3 x 230 V 7.0 A 1... View larger
Images are for illustrative purposes only. Please refer to data sheet for details

DB1-127D0FN-N2CC 197195 EATON ELECTRIC Cool Plate Frequency Converter Ent: 1 x 230V Salt: 3 x 230 V 7.0 A 1...

DB1-127D0FN-N2CC

197195

EATON - MOELLER

10 Pcs.

Cool Plate Frequency Converter; Ent: 1 x 230V; Salt: 3 x 230 V; 7.0 A; 1.5 kW; V/f, SLV; EMC Filter; IP20 Variable frequency drive, 230 V AC, 1-phase, 7 A, 1.5 kW, IP20/NEMA0, Radio interference suppression filter, Additional PCB protection, FS1B Variable frequency drive, Part group reference (e.g. DIL): DB1, Rated operational voltage: Ue = 230 V AC, 1-phase, 240 V AC, single-phase, Output voltage with Ve: U2 = 230 V AC, 3-phase, 240 V AC, 3-phase, Mains voltage (50/60Hz): ULN = 200 (-10%) - 240 (+10%) V, Rated operational current At 150% overload: Ie = 7 A, Note: Rated operational current at an operating frequency of 8 kHz and an ambient air temperature of +60°C, depending on cooling, Note: Overload cycle for 60 s every 600 s, Assigned motor rating Note: for normal internally and externally ventilated 4 pole , three-phase asynchronous motors with 1500 rpm-1 at 50 Hz or 1800 min-1 at 60 Hz, Overload cycle for 60 s every 600 s, at 230 V, 50 Hz, Assigned motor rating 150 % Overload: P = 1.5 kW, 150 % Overload: IM = 7 A, Assigned motor rating Note: at 220 - 240 V, 60 Hz, Assigned motor rating 150 % Overload: P = 2 HP, Assigned motor rating 150 % Overload: IM = 7 A, Degree of Protection: IP20/NEMA 0, Interface/field bus (built-in): OP-Bus (RS485)/Modbus RTU, CANopen®, Fitted with: Radio interference suppression filter, Frame size: FS1, Standards: General requirements: IEC/EN 61800-2, EMV requirements: IEC/EN 61800-3 , Safety requirements: IEC/EN 61800-5-1

Automation > Frequency converter less than 1 kV
Power XL Frequency Converters

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Variable frequency drive, 230 V AC, 1-phase, 7 A, 1.5 kW, IP20/NEMA0, Radio interference suppression filter, Additional PCB protection, FS1B
Variable frequency drive, Part group reference (e.g. DIL): DB1, Rated operational voltage: Ue = 230 V AC, 1-phase, 240 V AC, single-phase, Output voltage with Ve: U2 = 230 V AC, 3-phase, 240 V AC, 3-phase, Mains voltage (50/60Hz): ULN = 200 (-10%) - 240 (+10%) V, Rated operational current At 150% overload: Ie = 7 A, Note: Rated operational current at an operating frequency of 8 kHz and an ambient air temperature of +60°C, depending on cooling, Note: Overload cycle for 60 s every 600 s, Assigned motor rating Note: for normal internally and externally ventilated 4 pole, three-phase asynchronous motors with 1500 rpm-1 at 50 Hz or 1800 min-1 at 60 Hz, Overload cycle for 60 s every 600 s, at 230 V, 50 Hz, Assigned motor rating 150 % Overload: P = 1.5 kW, 150 % Overload: IM = 7 A, Assigned motor rating Note: at 220 - 240 V, 60 Hz, Assigned motor rating 150 % Overload: P = 2 HP, Assigned motor rating 150 % Overload: IM = 7 A, Degree of Protection: IP20/NEMA 0, Interface/field bus (built-in): OP-Bus (RS485)/Modbus RTU, CANopen®, Fitted with: Radio interference suppression filter, Frame size: FS1, Standards: General requirements: IEC/EN 61800-2, EMV requirements: IEC/EN 61800-3, Safety requirements: IEC/EN 61800-5-1

Delivery program

Photo
DB1-127D0FN-N2CC-LDB1-127D0FN-N2CC-CDB1-127D0FN-N2CC-R
Product range
Variable frequency drives
Part group reference (e.g. DIL)
DB1
Rated operational voltage [Ue]
230 V AC, 1-phase
240 V AC, single-phase
Output voltage with Ve[U2]
230 V AC, 3-phase
240 V AC, 3-phase
Mains voltage (50/60Hz) [ULN]
200 (-10%) - 240 (+10%) V
Rated operational current [Ie]
At 150% overload [Ie]
7 A
Note
Rated operational current at an operating frequency of 8 kHz and an ambient air temperature of +60°C
depending on cooling
Assigned motor rating
Note
for normal internally and externally ventilated 4 pole, three-phase asynchronous motors with 1500 rpm-1at 50 Hz or 1800 min-1at 60 Hz
Note
Overload cycle for 60 s every 600 s
Note
at 230 V, 50 Hz
150 % Overload [P]
1.5 kW
150 % Overload [IM]
7 A
Note
at 220 - 240 V, 60 Hz
150 % Overload [P]
2 HP
150 % Overload [IM]
7 A
Degree of Protection
IP20/NEMA0
Interface/field bus (built-in)
OP-Bus (RS485)/Modbus RTU, CANopen®
Fitted with
Radio interference suppression filter
Additional PCB protection
Parameterization
Keypad
Fieldbus
drivesConnect
drivesConnect mobile (App)
Frame size
FS1B
Connection to SmartWire-DT
no

Technical data

General
Standards
General requirements: IEC/EN 61800-2
EMV requirements: IEC/EN 61800-3
Safety requirements: IEC/EN 61800-5-1
Certifications
CE, UL, cUL, RCM
Production quality
RoHS, ISO 9001
Climatic proofing [ρw]
< 95%, average relative humidity (RH), non-condensing, non-corrosive %
Ambient temperatureOperating ambient temperature min.
-10 °C
Ambient temperatureOperating ambient temperature max.
+60 °C
Ambient temperature
operation (with 150 % overload)
Ambient temperatureStorage [ϑ]
-40 - +60 °C
Radio interference levelRadio interference class (EMC)
C1 (for conducted emissions only), C2, C3, depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Radio interference levelEnvironment (EMC)
1st and 2nd environments as per EN 61800-3
Radio interference levelmaximum motor cable length [I]
C1 ≤ 1 m
C2 ≤ 3 m
C3 ≤ 10 m m
Mechanical shock resistance
15 (11 m/s, EN 60068-2-27) g
Vibration
EN 61800-5-1
Mounting position
As required
depending on the cooling
Altitude
0 - 1000 m above sea level
Above 1000 m: 1% derating for every 100 m
max. 2000 m m
Degree of Protection
IP20/NEMA0
Protection against direct contact
BGV A3 (VBG4, finger- and back-of-hand proof)
Main circuit
SupplyRated operational voltage [Ue]
230 V AC, 1-phase
240 V AC, single-phase
SupplyMains voltage (50/60Hz) [ULN]
200 (-10%) - 240 (+10%) V
SupplyInput current (150% overload) [ILN]
15.5 A
SupplySystem configuration
AC supply systems with earthed center point
SupplySupply frequency [fLN]
50/60 Hz
SupplyFrequency range [fLN]
48 - 62 Hz
SupplyMains switch-on frequency
Maximum of one time every 30 seconds
Power sectionFunction
Variable frequency drive with internal DC link and IGBT inverter
Power sectionOverload current (150% overload) [IL]
10.5 A
Power sectionmax. starting current (High Overload) [IH]
175 %
Power sectionNote about max. starting current
for 3.75 seconds every 600 seconds
Power sectionOutput voltage with Ve[U2]
230 V AC, 3-phase
240 V AC, 3-phase
Power sectionOutput Frequency [f2]
0 - 50/60 (max. 500) Hz
Power sectionSwitching frequency [fPWM]
8
adjustable 4 - 32 (audible) kHz
Power sectionOperation Mode
U/f control
Speed control with slip compensation
sensorless vector control (SLV)
PM motors
Synchronous reluctance motors
BLDC motors
Power sectionFrequency resolution (setpoint value) [Δf]
0.1 Hz
Power sectionRated operational currentAt 150% overload [Ie]
7 A
Power sectionNote
Rated operational current at an operating frequency of 8 kHz and an ambient air temperature of +60°C
depending on cooling
Power sectionEfficiency [η]
95 %
Power sectionHeat dissipation at current/speed [%]Current = 100%Speed = 0 % [PV]
94.5 W
Power sectionHeat dissipation at current/speed [%]Current = 100%Speed = 50 % [PV]
86.9 W
Power sectionHeat dissipation at current/speed [%]Current = 100%Speed = 90 % [PV]
113.1 W
Power sectionHeat dissipation at current/speed [%]Current = 50 %Speed = 0 % [PV]
45.8 W
Power sectionHeat dissipation at current/speed [%]Current = 50 %Speed = 50 % [PV]
56.3 W
Power sectionHeat dissipation at current/speed [%]Current = 50 %Speed = 90 % [PV]
74.4 W
Power sectionHeat dissipation at current/speed [%]Current = 50 %Speed = 0 % [PV]
49.6 W
Power sectionHeat dissipation at current/speed [%]Current = 50 %Speed = 50 % [PV]
44.8 W
Power sectionMaximum leakage current to ground (PE) without motor [IPE]
3.5 (230 V) mA
Power sectionFan
temperature controlled
Tool-less swapping
Power sectionFitted with
Radio interference suppression filter
Additional PCB protection
Power sectionFrame size
FS1B
Motor feederNote
for normal internally and externally ventilated 4 pole, three-phase asynchronous motors with 1500 rpm-1at 50 Hz or 1800 min-1at 60 Hz
Motor feederNote
Overload cycle for 60 s every 600 s
Motor feederNote
at 230 V, 50 Hz
Motor feeder150 % Overload [P]
1.5 kW
Motor feederNote
at 220 - 240 V, 60 Hz
Motor feeder150 % Overload [P]
2 HP
Motor feedermaximum permissible cable length [I]
screened: 10 m
Motor feederApparent powerApparent power at rated operation 230 V [S]
1.61 kVA
Motor feederApparent powerApparent power at rated operation 240 V [S]
1.68 kVA
Motor feederBraking functionStandard braking torque
max. 30 % MN
Motor feederBraking functionDC braking torque
max. 100% of rated operational current Ie,variable
Control section
External control voltage [Uc]
24 V DC (max. 100 mA) V
Reference voltage [Us]
10 V DC (max. 10 mA) V
Analog inputs
2, parameterizable, 0 - 10 V DC, 0/4 - 20 mA
Analog outputs
1, parameterizable, 0 - 10 V
Digital inputs
4, parameterizable, max. 30 V DC
Digital outputs
1, parameterizable, 24 V DC
Relay outputs
1, parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1)
Interface/field bus (built-in)
OP-Bus (RS485)/Modbus RTU, CANopen®
Expansion slots
1
Assigned switching and protective elements
Power WiringSafety device (fuse or miniature circuit-breaker)IEC (Type B, gG), 150 %
FAZ-B16/1N
Power WiringSafety device (fuse or miniature circuit-breaker)UL (Class CC or J)
15 A
Power WiringMains contactor150 % overload (CT/IH, at 50 °C)
DILM7-… + DILM12-XP1
Power WiringMain choke150 % overload (CT/IH, at 50 °C)
DX-LN1-018
Power WiringRadio interference suppression filter (external, 150 %)
DX-EMC12-019-FS1
Motor feedermotor choke150 % overload (CT/IH, at 50 °C)
DX-LM3-008
Motor feederSine filter150 % overload (CT/IH, at 50 °C)
DX-SIN3-010

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation [In]
7 A
Heat dissipation per pole, current-dependent [Pvid]
0 W
Static heat dissipation, non-current-dependent [Pvs]
0 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-10 °C
Operating ambient temperature max.
+60 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Approvals

Product Standards
UL 508C; CSA-C22.2 No. 274; IEC/EN61800-2; IEC/EN61800-3; IEC/EN61800-5-1; CE marking
UL File No.
E172143
UL Category Control No.
NMMS2, NMMS8
CSA File No.
UL report applies to both US and Canada
North America Certification
UL listed, certified by UL for use in Canada
Specially designed for North America
No
Suitable for
Branch circuits
Max. Voltage Rating
1~ 240 V AC IEC: TN-S UL/CSA: "Y" (Solidly Grounded Wey)
Degree of Protection
IEC: IP20, NEMA 0

Dimensions

8230DIM-169

ETIM for 197195 Low-voltage industrial controls and switchgear (EC001857)
Feature Name Feature Value
Mains voltage (EF006780) 200 V
Mains frequency (EF006783) 50/60 Hz
Max. output frequency (EF007350) 500 Hz
Number of analogue outputs (EF001995) 1
Number of digital outputs (EF001993) 1
With control element (EF001538) No
Application in industrial area permitted (EF007294) No
Application in domestic- and commercial area permitted (EF007295) No
Supporting protocol for TCP/IP (EF003050) No
Supporting protocol for PROFIBUS (EF003052) No
Supporting protocol for CAN (EF003053) No
Supporting protocol for INTERBUS (EF003054) No
Supporting protocol for ASI (EF003051) No
Supporting protocol for KNX (EF003055) No
Supporting protocol for Modbus (EF003057) No
Supporting protocol for Data-Highway (EF003058) No
Supporting protocol for DeviceNet (EF003059) No
Supporting protocol for SUCONET (EF003060) No
Supporting protocol for LON (EF003017) No
Supporting protocol for PROFINET IO (EF007525) No
Supporting protocol for PROFINET CBA (EF007524) No
Supporting protocol for SERCOS (EF006657) No
Supporting protocol for Foundation Fieldbus (EF007522) No
Supporting protocol for EtherNet/IP (EF007521) No
Supporting protocol for AS-Interface Safety at Work (EF007519) No
Supporting protocol for DeviceNet Safety (EF007520) No
Supporting protocol for INTERBUS-Safety (EF006662) No
Supporting protocol for PROFIsafe (EF007526) No
Supporting protocol for SafetyBUS p (EF007527) No
Supporting protocol for BACnet (EF011944) No
Supporting protocol for other bus systems (EF003062) No
With optical interface (EF003028) No
With PC connection (EF006107) No
Integrated breaking resistance (EF007293) No
4-quadrant operation possible (EF006803) No
Degree of protection (IP) (EF005474) IP20
Height (EF000040) 130 mm
Width (EF000008) 118 mm
Depth (EF000049) 85 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.