EATON - MOELLER CL-PKZ0 CL-PKZ0 082881 Y7-82881 EATON ELECTRIC Current limiter, 3p, 63A, 400VAC/100kA, 690VAC/10kA View larger
Images are for illustrative purposes only. Please refer to data sheet for details

CL-PKZ0 082881 Y7-82881 EATON ELECTRIC Current limiter, 3p, 63A, 400VAC/100kA, 690VAC/10kA

CL-PKZ0

082881

Y7-82881

EATON - MOELLER

1 Pcs.

Current limiter, 3p, 63A, 400VAC/100kA, 690VAC/10kA 3-pole current limiter 63 A 400 V AC/100 Ka 690 V AC/10 kA Eaton Moeller® series PKZ0 Current limiter, 3p, 63A, 400VAC/100kA, 690VAC/10kA Current limiter 3pole, submountable with PKZM0-size circuit-breaker, PKZM4, PKZM01, Ue = 690 V, Iu = 63 A

Automation > Current limiter
Circuit Breakers PKZ

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

General specifications

Product Name
Eaton Moeller® series PKZ0 Current limiter
Catalog Number
082881
Model Code
CL-PKZ0
EAN
4015080828815
Product Length/Depth
56 mm
Product Height
90 mm
Product Width
45 mm
Product Weight
0.201 kg
Certifications
CSA Class No.: 3211-05
UL 508
CSA-C22.2 No. 14
IEC/EN 60947-4-1
CE
UL Category Control No.: NLRV
CSA
CSA File No.: 165628
UL
UL File No.: E36332

Features & Functions

Functions
Short-circuit current limiter
Can be used for individual and group protection

General

Mounting Method
DIN rail
Mounting position
Next to or behind the motor protective circuit breaker
Overvoltage category
III
Pollution degree
3
Product category
Accessories
Rated impulse withstand voltage (Uimp)
6000 V AC
Type
Motor-protective circuit-breaker, non-auto-protected in order to increase switching capacity

Climatic environmental conditions

Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C

Electrical rating

Rated uninterrupted current (Iu)
63 A

Short-circuit rating

Rated conditional short-circuit current (Iq)
0 kA

Design verification

Equipment heat dissipation, current-dependent Pvid
8.4 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
2.8 W
Rated operational current for specified heat dissipation (In)
63 A
Static heat dissipation, non-current-dependent Pvs
0 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

ETIM for 082881 Low-voltage industrial controls and switchgear (EC000239)
Feature Name Feature Value
Max. apparent power (EF008258) 0 VA
Mounting method (EF000003) DIN rail
Conditioned rated short-circuit current Iq (EF001444) 0 kA
Rated permanent current Iu (EF001389) 63 A
Short-circuit current limiter (EF007333) Yes

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.