View larger
DILA-40(42V50HZ,48V60HZ) 276325 Y7-276325 EATON ELECTRIC 051773 DILER-22(42V50HZ,48V60HZ)
DILA-40(42V50HZ,48V60HZ)
276325
Y7-276325
EATON - MOELLER
1 Pcs.
Automation > Contactor relay
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Engineered for alternating current systems, the Eaton Moeller DILA-40(42V50HZ,48V60HZ) contactor relay provides robust auxiliary contact expansion. Control panels utilize these relays to multiply switching paths, support safety logic, and interface secondary actuators within manufacturing plants. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Manufacturer: Eaton Moeller
- Manufacturer part number: DILA-40(42V50HZ,48V60HZ)
- Catalogue code: 276325
- Catalogue title: DILA-40(42V50HZ,48V60HZ) 276325 Y7-276325 EATON ELECTRIC 051773 DILER-22(42V50HZ,48V60HZ)
- Product description: General specifications Product Name Eaton Moeller® series DILA Control relay Catalog Number 276325 Model Code DILA-40(42V50HZ,48V60HZ) EAN 4015082763251 Product Length/Depth 75 mm Product Height 68 mm Product Width 45 mm
More info
▲General specifications
CSA Class No.: 3211-03
UL Category Control No.: NKCR
UL File No.: E29184
CSA-C22.2 No. 14-05
IEC/EN 60947
IEC/EN 60947-4-1
EN 60947-5-1
CSA
UL
UL 508
CSA File No.: 012528
VDE 0660
Features & Functions
General
7 g, N/O auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
2 x (0.75 - 2.5) mm², Screw terminals
1 x (0.75 - 4) mm², Screw terminals
2, Terminal screw, Pozidriv screwdriver
Electrical rating
4 A at 60 V, DC L/R ≤ 50 ms (with 3 contacts in series)
6 A at 110 V, DC L/R ≤ 15 ms (with 3 contacts in series)
6 A at 60 V, DC L/R ≤ 15 ms (with 1 contact in series)
1 A at 220 V, DC L/R ≤ 50 ms (with 3 contacts in series)
4 A at 24 V, DC L/R ≤ 50 ms (with 3 contacts in series)
10 A at 24 V, DC L/R ≤ 15 ms (with 1 contact in series)
2 A at 110 V, DC L/R ≤ 50 ms (with 3 contacts in series)
1 A at 220 V, DC L/R ≤ 15 ms (with 1 contact in series)
10 A at 60 V, DC L/R ≤ 15 ms (with 2 contacts in series)
5 A at 220 V, DC L/R ≤ 15 ms (with 3 contacts in series)
16 A
400 V AC, Between coil and auxiliary contacts, According to EN 61140
15 A, 600 V AC, (UL/CSA)
P300, DC operated (UL/CSA)