View larger
DILMP45-01(110V50HZ,120V60HZ) 118915 Y7-118915 EATON ELECTRIC 118915 DILMP45-01(110V50HZ,120V60HZ)
DILMP45-01(110V50HZ,120V60HZ)
118915
Y7-118915
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller DILMP45-01(110V50HZ,120V60HZ) contactor is designed for switching multi-pole electrical loads and non-inductive or slightly inductive loads in industrial automation layouts. These components ensure robust circuit control across varied manufacturing processes.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 110 V
- Rated control supply voltage AC 60 Hz (EF003979): 120 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Number of normally open contacts as main contact (EF001374): 4
- Type of electrical connection of main circuit (EF006819): Screw connection
- Operating voltage AC 50 Hz (EF008206): 24 V
- Operating voltage AC 60 Hz (EF008207): 24 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 45 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 25 A
- Rated operation power at AC-3, 400 V (EF001364): 11 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 15 A
- Rated operation power at AC-4, 400 V (EF008496): 7 kW
- Rated operation power NEMA (EF011960): 11 kW
- Modular version (EF001126): No
- Width (EF000008): 58 mm
More info
▲General specifications
UL
IEC/EN 60947-4-1
CSA-C22.2 No. 60947-4-1-14
UL 60947-4-1
CSA Class No.: 2411-03, 3211-04
VDE 0660
CE
CSA
UL Category Control No.: NLDX
IEC/EN 60947
UL File No.: E29096
Features & Functions
General
10,000,000 Operations (DC operated)
5000 mechanical Operations/h (AC operated)
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Ambient conditions, mechanical
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-3
Terminal capacities
2 x (0.75 - 1.5) mm²
2 x (0.75 - 2.5) mm²
1 x (0.75 - 16) mm², Main cables
2 x (0.75 - 10) mm², Main cables
2 x (0.75 - 2.5) mm², Control circuit cables
1 x (0.75 - 2.5) mm²
18 - 14, Control circuit cables
M3.5, Terminal screw, Control circuit cables
0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver
3 Nm, Screw terminals, Main cables
Electrical Rating
Short-circuit rating
5 kA, SCCR (UL/CSA)
125 A, max. CB, SCCR (UL/CSA)
10/100 kA, Fuse, SCCR (UL/CSA)
10/65 kA, CB, SCCR (UL/CSA)
50/32 A, max. CB, SCCR (UL/CSA)
10/100 kA, Fuse, SCCR (UL/CSA)
50/32 A, max. CB, SCCR (UL/CSA)
125/100 A, Class J, max. Fuse, SCCR (UL/CSA)
Conventional thermal current
Switching capacity
10 A, 600 V AC, (UL/CSA)
P300, DC operated (UL/CSA)
Switching time
Magnet system
0.8 - 1.1 V AC x Uc
50 VA, Dual-frequency coil in a cold state and 1.0 x Us
2.1 W, Dual-frequency coil in a cold state and 1.0 x Us
Motor Rating
Communication
Contacts
Safety
440 V AC, Between coil and contacts, According to EN 61140
Special purpose ratings
40 A (480V 60Hz 3phase, 277V 60Hz 1phase)
150 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
3 HP, 200 V 60 Hz 3-ph, (UL/CSA)
10 HP, 480 V 60 Hz 3-ph, (UL/CSA)
5 HP, 240 V 60 Hz 3-ph, (UL/CSA)
11 A, 200 V 60 Hz 3-ph, (UL/CSA)
14 A, 480 V 60 Hz 3-ph, (UL/CSA)
15 HP, 600 V 60 Hz 3-ph, (UL/CSA)
15.2 A, 240 V 60 Hz 3-ph, (UL/CSA)
240 A, LRA 480 V 60 Hz 3phase; (CSA)
40 A, FLA 480 V 60 Hz 3phase; (CSA)
30 A, FLA 600 V 60 Hz 3phase; (CSA)
40 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
40 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)