View larger
DILMP20(230V50/60HZ) 276978 Y7-276978 EATON ELECTRIC 276978 DILMP20(230V50/60HZ)
DILMP20(230V50/60HZ)
276978
Y7-276978
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller DILMP20(230V50/60HZ) is a 4-pole contactor engineered for reliable switching of multi-phase circuits and lighting or heating loads. Industrial contactors are vital elements in electrical enclosures, enabling automated control systems to manage power delivery safely and efficiently. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 230 V
- Rated control supply voltage AC 60 Hz (EF003979): 230 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Number of normally open contacts as main contact (EF001374): 4
- Type of electrical connection of main circuit (EF006819): Screw connection
- Operating voltage AC 50 Hz (EF008206): 24 V
- Operating voltage AC 60 Hz (EF008207): 24 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 22 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 12 A
- Rated operation power at AC-3, 400 V (EF001364): 5.5 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 10 A
- Rated operation power at AC-4, 400 V (EF008496): 4.5 kW
- Rated operation power NEMA (EF011960): 0 kW
- Modular version (EF001126): No
- Width (EF000008): 45 mm
More info
▲General specifications
CE
UL File No.: E29096
CSA Class No.: 2411-03, 3211-04
UL
UL Category Control No.: NLDX
VDE 0660
IEC/EN 60947
IEC/EN 60947-4-1
CSA-C22.2 No. 60947-4-1-14
CSA
UL 60947-4-1
Features & Functions
General
10,000,000 Operations (AC operated)
5000 mechanical Operations/h (DC operated)
AC-3: Normal AC induction motors: starting, switch off during running
Ambient conditions, mechanical
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
2 x (0.75 - 1.5) mm²
2 x (0.75 - 2.5) mm²
2 x (0.75 - 2.5) mm²
1 x (0.75 - 2.5) mm²
2, Terminal screw, Pozidriv screwdriver
Electrical Rating
Short-circuit rating
60 A, max. CB, SCCR (UL/CSA)
5 kA, SCCR (UL/CSA)
25 A, Class RK5, max. Fuse, SCCR (UL/CSA)
30 kA, Fuse, SCCR (UL/CSA)
Conventional thermal current
Switching capacity
Switching time
Magnet system
0.8 - 1.1 V AC/DC x Us
24 VA, Dual-frequency coil in a cold state and 1.0 x Us
1.4 W, Dual-frequency coil in a cold state and 1.0 x Us
Communication
Contacts
Safety
400 V AC, Between coil and contacts, According to EN 61140
Special purpose ratings
20 A (600V 60Hz 3phase, 347V 60Hz 1phase)
6.1 A, 600 V 60 Hz 3-ph, (UL/CSA)
60 A, LRA 480 V 60 Hz 3phase; (CSA)
10 A, FLA 480 V 60 Hz 3phase; (CSA)
60 A, LRA 600 V 60 Hz 3phase; (CSA)
20 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
14 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)