View larger
DILMP20(415V50HZ,480V60HZ) 276973 Y7-276973 EATON ELECTRIC Contactor, 4p, 20A / AC1
DILMP20(415V50HZ,480V60HZ)
276973
Y7-276973
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller DILMP20(415V50HZ,480V60HZ) functions as a 4-pole contactor designed for managing multi-phase loads and power distribution networks. Industrial facilities integrate these devices to control electrical circuits efficiently and safely. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 415 V
- Rated control supply voltage AC 60 Hz (EF003979): 480 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Number of normally open contacts as main contact (EF001374): 4
- Type of electrical connection of main circuit (EF006819): Screw connection
- Operating voltage AC 50 Hz (EF008206): 24 V
- Operating voltage AC 60 Hz (EF008207): 24 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 22 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 12 A
- Rated operation power at AC-3, 400 V (EF001364): 5.5 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 10 A
- Rated operation power at AC-4, 400 V (EF008496): 4.5 kW
- Rated operation power NEMA (EF011960): 0 kW
- Modular version (EF001126): No
- Width (EF000008): 45 mm
More info
▲General specifications
IEC/EN 60947
VDE 0660
IEC/EN 60947-4-1
UL 60947-4-1
UL Category Control No.: NLDX
CSA
CE
CSA-C22.2 No. 60947-4-1-14
UL
UL File No.: E29096
CSA Class No.: 2411-03, 3211-04
Features & Functions
General
10,000,000 Operations (DC operated)
5000 mechanical Operations/h (AC operated)
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Ambient conditions, mechanical
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
2 x (0.75 - 1.5) mm²
1 x (0.75 - 2.5) mm²
2 x (0.75 - 2.5) mm²
1 x (0.75 - 4) mm²
0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver
Electrical Rating
Short-circuit rating
60 A, max. CB, SCCR (UL/CSA)
45 A, max. Fuse, SCCR (UL/CSA)
25 A, Class RK5, max. Fuse, SCCR (UL/CSA)
25 A, Class RK5, max. Fuse, SCCR (UL/CSA)
Conventional thermal current
Switching capacity
Switching time
Magnet system
0.8 - 1.1 V AC x Uc
19 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
4 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Communication
Contacts
Safety
400 V AC, Between the contacts, According to EN 61140
Special purpose ratings
20 A (480V 60Hz 3phase, 277V 60Hz 1phase)
5 HP, 600 V 60 Hz 3-ph, (UL/CSA)
10 A, FLA 480 V 60 Hz 3phase; (CSA)
60 A, LRA 600 V 60 Hz 3phase; (CSA)
10 A, FLA 600 V 60 Hz 3phase; (CSA)
20 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
14 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)