View larger
DILMP20(400V50HZ,440V60HZ) 276972 Y7-276972 EATON ELECTRIC 293990 DILK12-11(400V50HZ,440V60HZ)
DILMP20(400V50HZ,440V60HZ)
276972
Y7-276972
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Multi-pole switching devices such as the Eaton Moeller DILMP20(400V50HZ,440V60HZ) are engineered to control complex electrical loads and motor drives within industrial installations. They ensure dependable circuit interruption and power routing across manufacturing automation architectures. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 400 V
- Rated control supply voltage AC 60 Hz (EF003979): 440 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Number of normally open contacts as main contact (EF001374): 4
- Type of electrical connection of main circuit (EF006819): Screw connection
- Operating voltage AC 50 Hz (EF008206): 24 V
- Operating voltage AC 60 Hz (EF008207): 24 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 22 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 12 A
- Rated operation power at AC-3, 400 V (EF001364): 5.5 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 10 A
- Rated operation power at AC-4, 400 V (EF008496): 4.5 kW
- Rated operation power NEMA (EF011960): 0 kW
- Modular version (EF001126): No
- Width (EF000008): 45 mm
More info
▲General specifications
CSA Class No.: 2411-03, 3211-04
UL
CSA
CE
UL 60947-4-1
UL Category Control No.: NLDX
CSA File No.: 012528
IEC/EN 60947-4-1
CSA-C22.2 No. 60947-4-1-14
IEC/EN 60947
UL File No.: E29096
Features & Functions
General
10,000,000 Operations (AC operated)
5000 mechanical Operations/h (DC operated)
AC-3: Normal AC induction motors: starting, switch off during running
Ambient conditions, mechanical
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
2 x (0.75 - 1.5) mm²
1 x (0.75 - 2.5) mm²
2 x (0.75 - 2.5) mm²
1 x (0.75 - 4) mm²
0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver
Electrical Rating
Short-circuit rating
45 A, max. Fuse, SCCR (UL/CSA)
5 kA, SCCR (UL/CSA)
25 A, Class RK5, max. Fuse, SCCR (UL/CSA)
30 kA, Fuse, SCCR (UL/CSA)
Conventional thermal current
Switching capacity
Switching time
Magnet system
0.8 - 1.1 V AC/DC x Us
24 VA, Dual-frequency coil in a cold state and 1.0 x Us
4 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Communication
Contacts
Safety
400 V AC, Between the contacts, According to EN 61140
Special purpose ratings
20 A (600V 60Hz 3phase, 347V 60Hz 1phase)
5 HP, 600 V 60 Hz 3-ph, (UL/CSA)
60 A, LRA 480 V 60 Hz 3phase; (CSA)
60 A, LRA 600 V 60 Hz 3phase; (CSA)
10 A, FLA 600 V 60 Hz 3phase; (CSA)
20 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
14 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)