View larger
DILMP160(RDC24) 109920 Y7-109920 EATON ELECTRIC Contactor, 4p, 160A/AC1
DILMP160(RDC24)
109920
Y7-109920
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
DILMP160(RDC24) 109920 Y7-109920 EATON ELECTRIC Contactor, 4p, 160A/AC1 produced by Eaton Moeller is a heavy-duty industrial switching element utilized for managing high-current power distribution and large multi-phase load currents.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 0 V
- Rated control supply voltage DC (EF003980): 24 V
- Voltage type for actuating (EF008242): DC
- Number of normally open contacts as main contact (EF001374): 4
- Type of electrical connection of main circuit (EF006819): Screw connection
- Operating voltage AC 50 Hz (EF008206): 230 V
- Operating voltage AC 60 Hz (EF008207): 230 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 160 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 95 A
- Rated operation power at AC-3, 400 V (EF001364): 45 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 65 A
- Rated operation power at AC-4, 400 V (EF008496): 33 kW
- Rated operation power NEMA (EF011960): 55 kW
- Modular version (EF001126): No
- Width (EF000008): 134 mm
More info
▲General specifications
VDE 0660
CE
IEC/EN 60947
UL
IEC/EN 60947-4-1
CSA-C22.2 No. 60947-4-1-14
UL File No.: E29096
CSA Class No.: 2411-03, 3211-04
CSA File No.: 012528
UL 60947-4-1
UL Category Control No.: NLDX
Features & Functions
General
10,000,000 Operations (AC operated)
3600 mechanical Operations/h (AC operated)
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Ambient conditions, mechanical
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
2 x (0.75 - 1.5) mm²
2 x (0.75 - 2.5) mm²
2 x (0.75 - 4) mm², Control circuit cables
1 x (0.75 - 2.5) mm²
18 - 14, Control circuit cables
2 x (16 - 95) mm², Main cables
M3.5, Terminal screw, Control circuit cables
5 mm AF, Hexagon socket-head spanner, Terminal screw, Main cables
0.8 x 5.5/1 x 6 mm, Terminal screw, Control circuit cables, Standard screwdriver
1.2 Nm, Screw terminals, Control circuit cables
Electrical Rating
Short-circuit rating
600 A, max. Fuse, SCCR (UL/CSA)
10 kA, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA)
30/100 kA, Fuse, SCCR (UL/CSA)
300/300 A, Class J, max. Fuse, SCCR (UL/CSA)
300/300 A, Class J, max. Fuse, SCCR (UL/CSA)
350 A, max. CB, SCCR (UL/CSA)
30/100 kA, Fuse, SCCR (UL/CSA)
Conventional thermal current
Switching capacity
Switching time
Magnet system
0.8 - 1.1 V AC/DC x Us
Motor Rating
Communication
Contacts
Safety
440 V AC, Between the contacts, According to EN 61140
Special purpose ratings
100 A (600V 60Hz 3phase, 347V 60Hz 1phase)
62.1 A, 200 V 60 Hz 3-ph, (UL/CSA)
75 HP, 600 V 60 Hz 3-ph, (UL/CSA)
77 A, 480 V 60 Hz 3-ph, (UL/CSA)
30 HP, 240 V 60 Hz 3-ph, (UL/CSA)
80 A, 240 V 60 Hz 3-ph, (UL/CSA)
77 A, 600 V 60 Hz 3-ph, (UL/CSA)
60 HP, 480 V 60 Hz 3-ph, (UL/CSA)
420 A, LRA 600 V 60 Hz 3phase; (CSA)
540 A, LRA 480 V 60 Hz 3phase; (CSA)
90 A, FLA 480 V 60 Hz 3phase; (CSA)
100 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
100 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)