View larger
DILM185A/22(RAC500) 139539 Y7-139539 EATON ELECTRIC Contactor, 3p+2N/O+2N/C, 90kW/400V/AC3
DILM185A/22(RAC500)
139539
Y7-139539
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors more than 170 A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller DILM185A/22(RAC500) 139539 Y7-139539 EATON ELECTRIC Contactor, 3p+2N/O+2N/C, 90kW/400V/AC3 is a heavy-duty industrial contactor engineered to manage high-power electrical loads and large motors. It provides reliable switching performance and circuit control in demanding manufacturing environments.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 480 V
- Rated control supply voltage AC 60 Hz (EF003979): 480 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Rail connection
- Operating voltage AC 50 Hz (EF008206): 480 V
- Operating voltage AC 60 Hz (EF008207): 480 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 337 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 185 A
- Rated operation power at AC-3, 400 V (EF001364): 90 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 136 A
- Rated operation power at AC-4, 400 V (EF008496): 75 kW
- Rated operation power NEMA (EF011960): 93 kW
- Modular version (EF001126): No
- Width (EF000008): 140 mm
More info
▲General specifications
UL 60947-4-1
CSA File No.: 2389068
CE
CSA-C22.2 No. 60947-4-1-14
IEC/EN 60947-4-1
CSA
UL Category Control No.: NLDX
VDE 0660
UL File No.: E29096
CSA Class No.: 3211-04
UL
Global
3000 mechanical Operations/h (AC operated)
10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
General
Damp heat, cyclic, to IEC 60068-2-30
3000 mechanical Operations/h (AC operated)
10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Climatic environmental conditions
1 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Control circuit cables
1/0 - 350 MCM, Main cables
M10, Terminal screw, Main connections
1.2 Nm, Screw terminals, Control circuit cables
Terminal capacities
220 A at up to 525 V (Individual compensation, three-phase capacitors, open)
336 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
1680 A, LRA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
280 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Electrical rating
700 A, max. Fuse, SCCR (UL/CSA)
10 kA, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA)
100 kA, Fuse, SCCR (UL/CSA)
350 A, max. CB, SCCR (UL/CSA)
50 kA, CB, SCCR (UL/CSA)
100 kA, Fuse, SCCR (UL/CSA)
350 A, max. CB, SCCR (UL/CSA)
220 A at up to 525 V (Individual compensation, three-phase capacitors, open)
336 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
1680 A, LRA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
280 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Short-circuit rating
Conventional thermal current Ith
15 A, 600 V AC, (UL/CSA)
A600, AC operated (UL/CSA)
Switching capacity
AC operated: 0.2 x US max - 0.4 x US min, AC operated
180 W, Pull-in power, Coil in a cold state and 1.0 x Us
210 VA, Pull-in power, Coil in a cold state and 1.0 x Us
2.1 W, Coil in a cold state and 1.0 x Us
2.6 VA, Coil in a cold state and 1.0 x Us
Magnet system
180 W, Pull-in power, Coil in a cold state and 1.0 x Us
210 VA, Pull-in power, Coil in a cold state and 1.0 x Us
2.1 W, Coil in a cold state and 1.0 x Us
2.6 VA, Coil in a cold state and 1.0 x Us