View larger
DILM820/22(RAC500) 208226 Y7-208226 EATON ELECTRIC Contactor, 3p+2N/O+2N/C, 450kW/400V/AC3
DILM820/22(RAC500)
208226
Y7-208226
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors more than 170 A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Contactor DILM820/22(RAC500) by Eaton Moeller is a heavy-duty switching component designed for managing high-capacity electrical loads and industrial motors. These devices enable safe, automated power distribution in large-scale manufacturing systems.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz: 480 V
- Rated control supply voltage AC 60 Hz: 480 V
- Rated control supply voltage DC: 250 V
- Voltage type for actuating: AC/DC
- Number of normally open contacts as main contact: 3
- Type of electrical connection of main circuit: Rail connection
- Operating voltage AC 50 Hz: 250 V
- Operating voltage AC 60 Hz: 250 V
- Rated operation current Ie at AC-1, 400 V: 1225 A
- Rated operation current Ie at AC-3, 400 V: 820 A
- Rated operation power at AC-3, 400 V: 450 kW
- Rated operation current Ie at AC-4, 400 V: 656 A
- Rated operation power at AC-4, 400 V: 355 kW
- Rated operation power NEMA: 522 kW
- Modular version: No
- Width: 250 mm
More info
▲General specifications
UL Category Control No.: NLDX
CE
CSA File No.: 012528
CSA Class No.: 3211-04
UL
UL File No.: E29096
IEC/EN 60947
UL 60947-4-1
VDE 0660
CSA-C22.2 No. 60947-4-1-14
IEC/EN 60947-4-1
General
5,000,000 Operations (AC operated)
200 Operations/h
1000 mechanical Operations/h (AC operated)
10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
AC-3: Normal AC induction motors: starting, switch off during running
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
2 x (0.75 - 2.5) mm², Control circuit cables
1 x (0.75 - 2.5) mm², Control circuit cables
2/0 - 500 MCM, Main cables
M3.5, Terminal screw, Control circuit cables
1.2 Nm, Screw terminals, Control circuit cables
Electrical rating
265 A at 690 V (Individual compensation, three-phase capacitors, open)
5400 A, LRA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
900 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
5400 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Short-circuit rating
42 kA, SCCR (UL/CSA)
2000 A, max. Fuse, SCCR (UL/CSA)
1200 A, max. CB, SCCR (UL/CSA)
85 kA, CB, SCCR (UL/CSA)
85 kA, Fuse, SCCR (UL/CSA)
1200 A, max. CB, SCCR (UL/CSA)
2000 A, max. Fuse, SCCR (UL/CSA)
85 kA, CB, SCCR (UL/CSA)
AC-1/Conventional thermal current Ith
Switching capacity
15 A, 600 V AC, (UL/CSA)
A600, AC operated (UL/CSA)
Magnet system
Sealing - Voltage drops (0.6 - 0.7 x Uc min: Contactor remains switched on
Sealing - Voltage interruptions (0 - 0.2 x Uc min ≤ 10 ms: Time is bridged successfully
Sealing - Pick-up phase (0 - 0.7 x Uc min: Contactor does not switch on
Sealing - Voltage drops (0.2 - 0.6 x Uc min) > 12 ms: Drop-out of the contactor
Sealing - Voltage drops (0.2 - 0.6 x Uc min ≤12 ms: Time is bridged successfully
Sealing - Excess voltage (1.15 - 1.3 x Uc max): Contactor remains switched on
Sealing - Pick-up phase (0.7 x Uc min - 1.15 x Uc max): Contactor switches on with certainty
0.2 x US max - 0.6 x US min, DC operated
0.7 - 1.15 V DC x Us
700 W, Pull-in power, Coil in a cold state and 1.0 x Us
800 VA, Pull-in power, Coil in a cold state and 1.0 x Us
28.8 VA, Coil in a cold state and 1.0 x Us
12.4 W, Coil in a cold state and 1.0 x Us