View larger
DILM650/22(RA110) 208218 Y7-208218 EATON ELECTRIC Contactor, 3p+2N/O+2N/C, 355kW/400V/AC3
DILM650/22(RA110)
208218
Y7-208218
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors more than 170 A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Engineered for massive industrial electrical systems, this Eaton Moeller DILM650/22(RA110) contactor handles extremely high-capacity power switching requirements. Large-scale manufacturing plants and heavy machinery operations utilize contactors of this scale to control primary motor drives and major distribution lines. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 48 V
- Rated control supply voltage AC 60 Hz (EF003979): 48 V
- Rated control supply voltage DC (EF003980): 48 V
- Voltage type for actuating (EF008242): AC/DC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Rail connection
- Operating voltage AC 50 Hz (EF008206): 48 V
- Operating voltage AC 60 Hz (EF008207): 48 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 1041 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 650 A
- Rated operation power at AC-3, 400 V (EF001364): 355 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 512 A
- Rated operation power at AC-4, 400 V (EF008496): 280 kW
- Rated operation power NEMA (EF011960): 373 kW
- Modular version (EF001126): No
- Width (EF000008): 250 mm
More info
▲General specifications
VDE 0660
CSA-C22.2 No. 60947-4-1-14
IEC/EN 60947
CSA
CSA Class No.: 3211-04
UL 60947-4-1
UL Category Control No.: NLDX
IEC/EN 60947-4-1
UL File No.: E29096
UL
CSA File No.: 012528
General
5,000,000 Operations (DC operated)
1000 mechanical Operations/h (AC operated)
1000 mechanical Operations/h (DC operated)
8 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
1 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Control circuit cables
18 - 14, Control circuit cables
M3.5, Terminal screw, Control circuit cables
1.2 Nm, Screw terminals, Control circuit cables
Electrical rating
265 A at 690 V (Individual compensation, three-phase capacitors, open)
725 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
725 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
4350 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Short-circuit rating
30 kA, SCCR (UL/CSA)
1200 A, max. CB, SCCR (UL/CSA)
85 kA, CB, SCCR (UL/CSA)
85 kA, Fuse, SCCR (UL/CSA)
1200 A, max. CB, SCCR (UL/CSA)
2000 A, max. Fuse, SCCR (UL/CSA)
85 kA, CB, SCCR (UL/CSA)
1200 A, max. CB, SCCR (UL/CSA)
AC-1/Conventional thermal current Ith
Switching capacity
15 A, 600 V AC, (UL/CSA)
P300, DC operated (UL/CSA)
Magnet system
Sealing - Voltage interruptions 0 - 0.2 x Uc min) > 10 ms: Drop-out of the contactor
Sealing - Pick-up phase (0.7 x Uc min - 1.15 x Uc max): Contactor switches on with certainty
Sealing - Pick-up phase (0 - 0.7 x Uc min: Contactor does not switch on
Sealing - Voltage drops (0.2 - 0.6 x Uc min) > 12 ms: Drop-out of the contactor
Sealing - Voltage drops (0.6 - 0.7 x Uc min: Contactor remains switched on
Sealing - Voltage interruptions (0 - 0.2 x Uc min ≤ 10 ms: Time is bridged successfully
Sealing - Excess voltage (1.15 - 1.3 x Uc max): Contactor remains switched on
AC operated: 0.2 x US max - 0.6 x US min, AC operated
0.7 - 1.15 V DC x Us
800 VA, Pull-in power, Coil in a cold state and 1.0 x Us
800 VA, Pull-in power, Coil in a cold state and 1.0 x Us
26.4 VA, Coil in a cold state and 1.0 x Us
26.4 VA, Coil in a cold state and 1.0 x Us