DILM400/22(RA250) 208209 Y7-208209 EATON ELECTRIC Contactor, 3p+2N/O+2N/C, 200kW/400V/AC3
DILM400/22(RA250)
208209
Y7-208209
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors more than 170 A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller DILM400/22(RA250) is a heavy-duty power contactor built to manage extremely large electrical loads and high-power industrial motors. Large-scale automation systems depend on these high-capacity switching devices to handle high current loads safely. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Manufacturer: Eaton Moeller
- Manufacturer part number: DILM400/22(RA250)
- Catalogue code: 208209
- Catalogue title: DILM400/22(RA250) 208209 Y7-208209 EATON ELECTRIC Contactor, 3p+2N/O+2N/C, 200kW/400V/AC3
- Product description: General specifications Product Name Eaton Moeller® series DILM Contactor Catalog Number 208209 Model Code DILM400/22(RA250) EAN 4015082082093 Product Length/Depth 216 mm Product Height 209 mm Product Width 160 mm Product
- Manufacturer summary: Contactor, 3p+2N/O+2N/C, 200kW/400V/AC3 DILM400/22(RA250) Eaton Moeller® series DILM Contactor, 380 V 400 V 212 kW, 2 N/O, 2 NC, RA 250: 110 - 250 V 40 - 60 Hz/110 - 350 V DC, AC and DC operation, Screw connection
More info
▲General specifications
UL 60947-4-1
UL Category Control No.: NLDX
CSA Class No.: 3211-04
IEC/EN 60947-4-1
VDE 0660
UL/CSA
CSA file No. 012528
North America (UL listed, CSA certified)
EN 45545: Fire protection on railway vehicles
IEC 61373: Vibration and shock, tested for category 1 class B
CE marking
Global
7,000,000 Operations (AC operated)
2000 mechanical Operations/h (AC operated)
2000 mechanical Operations/h (DC operated)
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
General
Damp heat, constant, to IEC 60068-2-78
7,000,000 Operations (AC operated)
2000 mechanical Operations/h (AC operated)
2000 mechanical Operations/h (DC operated)
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Climatic environmental conditions
2 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Control circuit cables
18 - 14, Control circuit cables
M3.5, Terminal screw, Control circuit cables
1.2 Nm, Screw terminals, Control circuit cables
Terminal capacities
177 A at 690 V (Individual compensation, three-phase capacitors, open)
3120 A, LRA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
3300 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
420 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Electrical rating
30 kA, SCCR (UL/CSA)
800 A, max. Fuse, SCCR (UL/CSA)
600 A, max. CB, SCCR (UL/CSA)
800/600 A, Class J, max. Fuse, SCCR (UL/CSA)
100 kA, CB, SCCR (UL/CSA)
600 A, max. CB, SCCR (UL/CSA)
800/600 A, Class J, max. Fuse, SCCR (UL/CSA)
30/100 kA, Fuse, SCCR (UL/CSA)
177 A at 690 V (Individual compensation, three-phase capacitors, open)
3120 A, LRA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
3300 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
420 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Short-circuit rating
Conventional thermal current Ith
1 A, 250 V DC, (UL/CSA)
P300, DC operated (UL/CSA)
Switching capacity
Sealing - Pick-up phase (0.7 x Uc min - 1.15 x Uc max): Contactor switches on with certainty
Sealing - Voltage drops (0.6 - 0.7 x Uc min: Contactor remains switched on
Sealing - Pick-up phase (0 - 0.7 x Uc min: Contactor does not switch on
Sealing - Voltage drops (0.2 - 0.6 x Uc min) > 12 ms: Drop-out of the contactor
Sealing - Excess voltage (1.15 - 1.3 x Uc max): Contactor remains switched on
Sealing - Voltage drops (0.2 - 0.6 x Uc min ≤12 ms: Time is bridged successfully
Sealing - Voltage interruptions (0 - 0.2 x Uc min ≤ 10 ms: Time is bridged successfully
0.2 x US max - 0.6 x US min, DC operated
0.7 - 1.15 V DC x Us
450 VA, Pull-in power, Coil in a cold state and 1.0 x Us
450 VA, Pull-in power, Coil in a cold state and 1.0 x Us
14.2 VA, Coil in a cold state and 1.0 x Us
7.9 W, Coil in a cold state and 1.0 x Us
Magnet system
450 VA, Pull-in power, Coil in a cold state and 1.0 x Us
450 VA, Pull-in power, Coil in a cold state and 1.0 x Us
14.2 VA, Coil in a cold state and 1.0 x Us
7.9 W, Coil in a cold state and 1.0 x Us