Built for extreme power management applications, this Eaton Moeller Contactor, 3p+2N/O+2N/C, 2000A/AC1 controls massive electrical loads in heavy industrial plants and power distribution grids. Ultra-high-current contactors safely manage primary power distribution paths under automated system control. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 230 V
- Rated control supply voltage AC 60 Hz (EF003979): 230 V
- Rated control supply voltage DC (EF003980): 230 V
- Voltage type for actuating (EF008242): AC/DC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Rail connection
- Operating voltage AC 50 Hz (EF008206): 230 V
- Operating voltage AC 60 Hz (EF008207): 230 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 2450 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 0 A
- Rated operation power at AC-3, 400 V (EF001364): 0 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 0 A
- Rated operation power at AC-4, 400 V (EF008496): 0 kW
- Rated operation power NEMA (EF011960): 0 kW
- Modular version (EF001126): No
- Width (EF000008): 515 mm
More info
▲General specifications
IEC/EN 60947
CSA-C22.2 No. 60947-4-1-14
UL
CSA
UL 60947-4-1
CSA File No.: 012528
CCC
UL Category Control No.: NLDX
CE
IEC/EN 60947-4-1
VDE 0660
CSA Class No.: 3211-04
General
5,000,000 Operations (DC operated)
1000 mechanical Operations/h (DC operated)
8 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
1 x (0.75 - 2.5) mm², Control circuit cables
1 x (0.75 - 2.5) mm², Control circuit cables
M3.5, Terminal screw, Control circuit cables
0.8 x 5.5/1 x 6 mm, Terminal screw, Control circuit cables, Standard screwdriver
35 Nm, Main cable connection screw/bolt
Electrical rating
2000 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
AC-1/Conventional thermal current Ith
Switching capacity
1 A, 250 V DC, (UL/CSA)
P300, DC operated (UL/CSA)
Magnet system
Sealing - Voltage interruptions (0 - 0.2 x Uc min ≤ 10 ms: Time is bridged successfully
Sealing - Excess voltage (1.15 - 1.3 x Uc max): Contactor remains switched on
Sealing - Pick-up phase (0.7 x Uc min - 1.15 x Uc max): Contactor switches on with certainty
Sealing - Voltage drops (0.2 - 0.6 x Uc min ≤12 ms: Time is bridged successfully
Sealing - Pick-up phase (0 - 0.7 x Uc min: Contactor does not switch on
Sealing - Voltage interruptions 0 - 0.2 x Uc min) > 10 ms: Drop-out of the contactor
Sealing - Voltage drops (0.6 - 0.7 x Uc min: Contactor remains switched on
AC operated: 0.2 x US max - 0.6 x US min, AC operated
0.7 - 1.15 V AC x Us
1600 VA, Pull-in power, Coil in a cold state and 1.0 x Us
1400 W, Pull-in power, Coil in a cold state and 1.0 x Us
36.5 VA, Coil in a cold state and 1.0 x Us