View larger
DILM300A-S/22(220-240V50/60HZ) 139559 Y7-139559 EATON ELECTRIC Contactor, 3p+2N/O+2N/C, 160kW/400V/AC3
DILM300A-S/22(220-240V50/60HZ)
139559
Y7-139559
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors more than 170 A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller DILM300A-S/22 contactor is a high-capacity switching solution built for heavy industrial motor control and large-scale power distribution systems requiring robust performance. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 220 V
- Rated control supply voltage AC 60 Hz (EF003979): 220 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Rail connection
- Operating voltage AC 50 Hz (EF008206): 220 V
- Operating voltage AC 60 Hz (EF008207): 220 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 490 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 300 A
- Rated operation power at AC-3, 400 V (EF001364): 160 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 240 A
- Rated operation power at AC-4, 400 V (EF008496): 132 kW
- Rated operation power NEMA (EF011960): 186 kW
- Modular version (EF001126): No
- Width (EF000008): 140 mm
More info
▲General specifications
CSA Class No.: 3211-04
IEC/EN 60947-4-1
VDE 0660
UL File No.: E29096
UL 60947-4-1
UL/CSA
CSA File No. 1017510
North America (UL listed, CSA certified)
EN 45545: Fire protection on railway vehicles
IEC 61373: Vibration and shock, tested for category 1 class B
CE marking
General
200 Operations/h
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
1 x (0.75 - 2.5) mm², Control circuit cables
1 x (0.75 - 2.5) mm², Control circuit cables
2/0 - 500 MCM, Main cables
M10, Terminal screw, Main connections
1.2 Nm, Screw terminals, Control circuit cables
Electrical rating
177 A at 690 V (Individual compensation, three-phase capacitors, open)
300 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
2160 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
360 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Short-circuit rating
700 A, max. Fuse, SCCR (UL/CSA)
18 kA, SCCR (UL/CSA)
18 kA, Fuse, SCCR (UL/CSA)
250 A, max. CB, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA)
700 A, Class L/450 A, Class J, max. Fuse, SCCR (UL/CSA)
18/100 kA, Fuse, SCCR (UL/CSA)
18 kA, CB, SCCR (UL/CSA)
600 A, max. CB, SCCR (UL/CSA)
700 A, Class J, max. Fuse, SCCR (UL/CSA)
700 A, Class L/450 A, Class J, max. Fuse, SCCR (UL/CSA)
18/100 kA, Fuse, SCCR (UL/CSA)
AC-1/Conventional thermal current Ith
Switching capacity
15 A, 600 V AC, (UL/CSA)
P300, DC operated (UL/CSA)
Magnet system
Sealing - Excess voltage (1.15 - 1.3 x Uc max): Contactor remains switched on
Sealing - Voltage interruptions (0 - 0.2 x Uc min ≤ 10 ms: Time is bridged successfully
Sealing - Voltage drops (0.2 - 0.6 x Uc min) > 12 ms: Drop-out of the contactor
Sealing - Pick-up phase (0 - 0.7 x Uc min: Contactor does not switch on
Sealing - Pick-up phase (0.7 x Uc min - 1.15 x Uc max): Contactor switches on with certainty
Sealing - Voltage drops (0.2 - 0.6 x Uc min ≤12 ms: Time is bridged successfully
Sealing - Voltage drops (0.6 - 0.7 x Uc min: Contactor remains switched on
AC operated: 0.25 x US max - 0.6 x US min, AC operated
325 W, Pull-in power, Coil in a cold state and 1.0 x Us
325 W, Pull-in power, Coil in a cold state and 1.0 x Us
7.3 VA, Coil in a cold state and 1.0 x Us
7.3 VA, Coil in a cold state and 1.0 x Us