DILM300A-S/22(110-120V50/60HZ) 139558 Y7-139558 EATON ELECTRIC Contactor, 3p+2N/O+2N/C, 160kW/400V/AC3
DILM300A-S/22(110-120V50/60HZ)
139558
Y7-139558
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors more than 170 A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller DILM300A-S/22(110-120V50/60HZ) contractor is an electromechanical switching device utilized for repeatedly establishing and interrupting electrical power circuits, most commonly for controlling heavy industrial electric motors and heating loads.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 110 V
- Rated control supply voltage AC 60 Hz (EF003979): 110 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Rail connection
- Operating voltage AC 50 Hz (EF008206): 110 V
- Operating voltage AC 60 Hz (EF008207): 110 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 490 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 300 A
- Rated operation power at AC-3, 400 V (EF001364): 160 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 240 A
- Rated operation power at AC-4, 400 V (EF008496): 132 kW
- Rated operation power NEMA (EF011960): 186 kW
- Modular version (EF001126): No
- Width (EF000008): 140 mm
More info
▲General specifications
CSA Class No.: 3211-04
UL 60947-4-1
VDE 0660
UL File No.: E29096
IEC/EN 60947-4-1
UL/CSA
CSA File No. 1017510
North America (UL listed, CSA certified)
EN 45545: Fire protection on railway vehicles
IEC 61373: Vibration and shock, tested for category 1 class B
CE marking
General
200 Operations/h
8 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
1 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Control circuit cables
18 - 14, Control circuit cables
M10, Terminal screw, Main connections
24 Nm, Main cable connection screw/bolt
Electrical rating
177 A at 690 V (Individual compensation, three-phase capacitors, open)
300 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
2160 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
360 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Short-circuit rating
600 A, max. CB, SCCR (UL/CSA)
700 A, max. Fuse, SCCR (UL/CSA)
250 A, max. CB, SCCR (UL/CSA)
700 A, Class L, max. Fuse, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA)
700 A, Class L/450 A, Class J, max. Fuse, SCCR (UL/CSA)
18/100 kA, Fuse, SCCR (UL/CSA)
18 kA, Fuse, SCCR (UL/CSA)
18 kA, CB, SCCR (UL/CSA)
600 A, max. CB, SCCR (UL/CSA)
700 A, Class L/450 A, Class J, max. Fuse, SCCR (UL/CSA)
18/100 kA, Fuse, SCCR (UL/CSA)
AC-1/Conventional thermal current Ith
Switching capacity
1 A, 250 V DC, (UL/CSA)
A600, AC operated (UL/CSA)
Magnet system
Sealing - Voltage drops (0.2 - 0.6 x Uc min) > 12 ms: Drop-out of the contactor
Sealing - Voltage drops (0.2 - 0.6 x Uc min ≤12 ms: Time is bridged successfully
Sealing - Voltage drops (0.6 - 0.7 x Uc min: Contactor remains switched on
Sealing - Pick-up phase (0.7 x Uc min - 1.15 x Uc max): Contactor switches on with certainty
Sealing - Voltage interruptions 0 - 0.2 x Uc min) > 10 ms: Drop-out of the contactor
Sealing - Excess voltage (1.15 - 1.3 x Uc max): Contactor remains switched on
Sealing - Voltage interruptions (0 - 0.2 x Uc min ≤ 10 ms: Time is bridged successfully
AC operated: 0.25 x US max - 0.6 x US min, AC operated
360 VA, Pull-in power, Coil in a cold state and 1.0 x Us
360 VA, Pull-in power, Coil in a cold state and 1.0 x Us
6.7 VA, Coil in a cold state and 1.0 x Us
4.2 W, Coil in a cold state and 1.0 x Us