DILM300A/22(RA250)
139556
Y7-139556
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors more than 170 A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller DILM300A/22(RA250) contactor is a heavy-duty industrial switching device designed for high-capacity motor loads and demanding power distribution tasks. Large-scale plants use such contactors to maintain operational safety. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 110 V
- Rated control supply voltage AC 60 Hz (EF003979): 110 V
- Rated control supply voltage DC (EF003980): 110 V
- Voltage type for actuating (EF008242): AC/DC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Rail connection
- Operating voltage AC 50 Hz (EF008206): 110 V
- Operating voltage AC 60 Hz (EF008207): 110 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 490 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 300 A
- Rated operation power at AC-3, 400 V (EF001364): 160 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 240 A
- Rated operation power at AC-4, 400 V (EF008496): 132 kW
- Rated operation power NEMA (EF011960): 186 kW
- Modular version (EF001126): No
- Width (EF000008): 140 mm
More info
▲General specifications
UL File No.: E29096
UL Category Control No.: NLDX
UL 60947-4-1
IEC/EN 60947-4-1
CSA Class No.: 3211-04
UL/CSA
CSA File No. 1017510
North America (UL listed, CSA certified)
EN 45545: Fire protection on railway vehicles
IEC 61373: Vibration and shock, tested for category 1 class B
CE marking
General
10,000,000 Operations (AC operated)
200 Operations/h
3000 mechanical Operations/h (AC operated)
10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
8 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-3: Normal AC induction motors: starting, switch off during running
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
1 x (0.75 - 2.5) mm², Control circuit cables
1 x (0.75 - 2.5) mm², Control circuit cables
18 - 14, Control circuit cables
M10, Terminal screw, Main connections
1.2 Nm, Screw terminals, Control circuit cables
Electrical rating
307 A at up to 525 V (Individual compensation, three-phase capacitors, open)
1800 A, LRA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
300 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
360 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Short-circuit rating
600 A, max. CB, SCCR (UL/CSA)
18 kA, SCCR (UL/CSA)
18 kA, Fuse, SCCR (UL/CSA)
700 A, Class L, max. Fuse, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA)
700 A, Class L/450 A, Class J, max. Fuse, SCCR (UL/CSA)
18/100 kA, Fuse, SCCR (UL/CSA)
18 kA, CB, SCCR (UL/CSA)
18 kA, Fuse, SCCR (UL/CSA)
600 A, max. CB, SCCR (UL/CSA)
700 A, Class L/450 A, Class J, max. Fuse, SCCR (UL/CSA)
18/100 kA, Fuse, SCCR (UL/CSA)
AC-1/Conventional thermal current Ith
Switching capacity
1 A, 250 V DC, (UL/CSA)
P300, DC operated (UL/CSA)
Magnet system
Sealing - Voltage drops (0.2 - 0.6 x Uc min) > 12 ms: Drop-out of the contactor
Sealing - Voltage drops (0.6 - 0.7 x Uc min: Contactor remains switched on
Sealing - Voltage interruptions 0 - 0.2 x Uc min) > 10 ms: Drop-out of the contactor
Sealing - Excess voltage (1.15 - 1.3 x Uc max): Contactor remains switched on
Sealing - Pick-up phase (0 - 0.7 x Uc min: Contactor does not switch on
Sealing - Voltage drops (0.2 - 0.6 x Uc min ≤12 ms: Time is bridged successfully
Sealing - Voltage interruptions (0 - 0.2 x Uc min ≤ 10 ms: Time is bridged successfully
0.2 x US max - 0.6 x US min, DC operated
0.7 - 1.15 V DC x Us
Control transformer with uk ≤ 6%
380 VA, Pull-in power, Coil in a cold state and 1.0 x Us
380 VA, Pull-in power, Coil in a cold state and 1.0 x Us
10.5 VA, Coil in a cold state and 1.0 x Us
5.5 W, Coil in a cold state and 1.0 x Us