View larger
DILM250/22(RAC500) 208202 Y7-208202 EATON ELECTRIC XTCE250L22C Contactor 3P 250A (AC-3,400V), auxiliar 2NA+2..
DILM250/22(RAC500)
208202
Y7-208202
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors more than 170 A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Engineered for massive electrical loads, the DILM250/22(RAC500) 208202 Y7-208202 EATON ELECTRIC Contactor provides high-capacity switching performance for heavy industrial systems. Industrial contactors manage the connection of multi-phase power supplies to large motors and heavy-duty distribution networks.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 480 V
- Rated control supply voltage AC 60 Hz (EF003979): 480 V
- Rated control supply voltage DC (EF003980): 250 V
- Voltage type for actuating (EF008242): AC/DC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Rail connection
- Operating voltage AC 50 Hz (EF008206): 250 V
- Operating voltage AC 60 Hz (EF008207): 250 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 429 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 250 A
- Rated operation power at AC-3, 400 V (EF001364): 132 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 200 A
- Rated operation power at AC-4, 400 V (EF008496): 110 kW
- Rated operation power NEMA (EF011960): 149 kW
- Modular version (EF001126): No
- Width (EF000008): 140 mm
More info
▲General specifications
UL 60947-4-1
UL Category Control No.: NLDX
VDE 0660
UL File No.: E29096
IEC/EN 60947-4-1
UL/CSA
CSA File No. 1017510
North America (UL listed, CSA certified)
EN 45545: Fire protection on railway vehicles
IEC 61373: Vibration and shock, tested for category 1 class B
CE marking
Global
10,000,000 Operations (AC operated)
200 Operations/h
3000 mechanical Operations/h (AC operated)
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
General
Damp heat, constant, to IEC 60068-2-78
10,000,000 Operations (AC operated)
200 Operations/h
3000 mechanical Operations/h (AC operated)
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Climatic environmental conditions
1 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Control circuit cables
2/0 - 500 MCM, Main cables
M10, Terminal screw, Main connections
24 Nm, Main cable connection screw/bolt
Terminal capacities
133 A at 690 V (Individual compensation, three-phase capacitors, open)
500 V AC, Between coil and contacts, According to EN 61140
250 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
300 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
2050 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Electrical rating
700 A, max. Fuse, SCCR (UL/CSA)
18 kA, SCCR (UL/CSA)
250 A, max. CB, SCCR (UL/CSA)
18 kA, Fuse, SCCR (UL/CSA)
700 A, Class L, max. Fuse, SCCR (UL/CSA)
18 kA, CB, SCCR (UL/CSA)
18 kA, Fuse, SCCR (UL/CSA)
600 A, max. CB, SCCR (UL/CSA)
133 A at 690 V (Individual compensation, three-phase capacitors, open)
500 V AC, Between coil and contacts, According to EN 61140
250 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
300 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
2050 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Short-circuit rating
Conventional thermal current Ith
1 A, 250 V DC, (UL/CSA)
P300, DC operated (UL/CSA)
Switching capacity
Sealing - Voltage interruptions 0 - 0.2 x Uc min) > 10 ms: Drop-out of the contactor
Sealing - Pick-up phase (0.7 x Uc min - 1.15 x Uc max): Contactor switches on with certainty
Sealing - Voltage drops (0.2 - 0.6 x Uc min ≤12 ms: Time is bridged successfully
Sealing - Voltage drops (0.2 - 0.6 x Uc min) > 12 ms: Drop-out of the contactor
Sealing - Voltage interruptions (0 - 0.2 x Uc min ≤ 10 ms: Time is bridged successfully
Sealing - Voltage drops (0.6 - 0.7 x Uc min: Contactor remains switched on
Sealing - Pick-up phase (0 - 0.7 x Uc min: Contactor does not switch on
0.2 x US max - 0.6 x US min, DC operated
0.7 - 1.15 V DC x Us
380 VA, Pull-in power, Coil in a cold state and 1.0 x Us
380 VA, Pull-in power, Coil in a cold state and 1.0 x Us
17.7 VA, Coil in a cold state and 1.0 x Us
10.8 W, Coil in a cold state and 1.0 x Us
Magnet system
380 VA, Pull-in power, Coil in a cold state and 1.0 x Us
380 VA, Pull-in power, Coil in a cold state and 1.0 x Us
17.7 VA, Coil in a cold state and 1.0 x Us
10.8 W, Coil in a cold state and 1.0 x Us