View larger
DILM250/22(RA110) 208200 Y7-208200 EATON ELECTRIC XTCE250L22Y Contactor 3P 250A (AC-3,400V), auxiliary 2NO +..
DILM250/22(RA110)
208200
Y7-208200
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors more than 170 A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller contactor, model DILM250/22(RA110), is a high-capacity switching component designed for heavy-duty motor control and industrial power distribution systems. Such contactors are utilized globally to safely handle large electrical loads, offering robust circuit isolation and durable mechanical operation under demanding operating conditions. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 48 V
- Rated control supply voltage AC 60 Hz (EF003979): 48 V
- Rated control supply voltage DC (EF003980): 48 V
- Voltage type for actuating (EF008242): AC/DC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Rail connection
- Operating voltage AC 50 Hz (EF008206): 48 V
- Operating voltage AC 60 Hz (EF008207): 48 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 429 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 250 A
- Rated operation power at AC-3, 400 V (EF001364): 132 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 200 A
- Rated operation power at AC-4, 400 V (EF008496): 110 kW
- Rated operation power NEMA (EF011960): 149 kW
- Modular version (EF001126): No
- Width (EF000008): 140 mm
More info
▲General specifications
UL Category Control No.: NLDX
CSA Class No.: 3211-04
VDE 0660
UL 60947-4-1
UL File No.: E29096
UL/CSA
CSA File No. 1017510
North America (UL listed, CSA certified)
EN 45545: Fire protection on railway vehicles
IEC 61373: Vibration and shock, tested for category 1 class B
CE marking
General
10,000,000 Operations (DC operated)
3000 mechanical Operations/h (AC operated)
3000 mechanical Operations/h (DC operated)
10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-3: Normal AC induction motors: starting, switch off during running
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
2 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Control circuit cables
18 - 14, Control circuit cables
M3.5, Terminal screw, Control circuit cables
1.2 Nm, Screw terminals, Control circuit cables
Electrical rating
220 A at up to 525 V (Individual compensation, three-phase capacitors, open)
500 V AC, Between the contacts, According to EN 61140
300 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
1800 A, LRA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
250 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Short-circuit rating
700 A, max. Fuse, SCCR (UL/CSA)
18 kA, SCCR (UL/CSA)
700 A, Class L, max. Fuse, SCCR (UL/CSA)
250 A, max. CB, SCCR (UL/CSA)
18 kA, Fuse, SCCR (UL/CSA)
700 A, Class L/450 A, Class J, max. Fuse, SCCR (UL/CSA)
18/100 kA, Fuse, SCCR (UL/CSA)
700 A, Class J, max. Fuse, SCCR (UL/CSA)
600 A, max. CB, SCCR (UL/CSA)
18 kA, CB, SCCR (UL/CSA)
700 A, Class L/450 A, Class J, max. Fuse, SCCR (UL/CSA)
18/100 kA, Fuse, SCCR (UL/CSA)
Conventional thermal current Ith
Switching capacity
15 A, 600 V AC, (UL/CSA)
P300, DC operated (UL/CSA)
Magnet system
Sealing - Voltage interruptions (0 - 0.2 x Uc min ≤ 10 ms: Time is bridged successfully
Sealing - Voltage drops (0.2 - 0.6 x Uc min) > 12 ms: Drop-out of the contactor
Sealing - Pick-up phase (0 - 0.7 x Uc min: Contactor does not switch on
Sealing - Voltage drops (0.2 - 0.6 x Uc min ≤12 ms: Time is bridged successfully
Sealing - Voltage drops (0.6 - 0.7 x Uc min: Contactor remains switched on
Sealing - Excess voltage (1.15 - 1.3 x Uc max): Contactor remains switched on
Sealing - Voltage interruptions 0 - 0.2 x Uc min) > 10 ms: Drop-out of the contactor
AC operated: 0.2 x US max - 0.6 x US min, AC operated
0.7 - 1.15 V AC x Us
380 VA, Pull-in power, Coil in a cold state and 1.0 x Us
250 W, Pull-in power, Coil in a cold state and 1.0 x Us
4.3 W, Coil in a cold state and 1.0 x Us
4.3 W, Coil in a cold state and 1.0 x Us