View larger
DILM225A/22(RDC130) 139552 Y7-139552 EATON ELECTRIC Contactor, 3p+2N/O+2N/C, 110kW/400V/AC3
DILM225A/22(RDC130)
139552
Y7-139552
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors more than 170 A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Engineered for high-capacity applications, an Eaton Moeller heavy-duty contactor manages significant electrical loads in large-scale industrial distribution networks and complex motor setups. These devices offer high durability and reliable performance under continuous operation. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 0 V
- Rated control supply voltage DC (EF003980): 110 V
- Voltage type for actuating (EF008242): DC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Rail connection
- Rated operation current Ie at AC-1, 400 V (EF001393): 356 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 225 A
- Rated operation power at AC-3, 400 V (EF001364): 110 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 164 A
- Rated operation power at AC-4, 400 V (EF008496): 90 kW
- Rated operation power NEMA (EF011960): 111 kW
- Modular version (EF001126): No
- Width (EF000008): 140 mm
- Height (EF000040): 190 mm
- Depth (EF000049): 158 mm
More info
▲General specifications
UL Category Control No.: NLDX
CE
IEC/EN 60947
IEC/EN 60947-4-1
UL
VDE 0660
UL 60947-4-1
CSA-C22.2 No. 60947-4-1-14
CSA File No.: 2389068
CSA Class No.: 3211-04
CSA
General
3000 mechanical Operations/h (DC operated)
10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
8 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
AC-3: Normal AC induction motors: starting, switch off during running
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
2 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Control circuit cables
18 - 14, Control circuit cables
M3.5, Terminal screw, Control circuit cables
24 Nm, Main cable connection screw/bolt
Electrical rating
133 A at 690 V (Individual compensation, three-phase capacitors, open)
336 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
1680 A, LRA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
280 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Short-circuit rating
10 kA, SCCR (UL/CSA)
700 A, max. Fuse, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA)
100 kA, Fuse, SCCR (UL/CSA)
350 A, max. CB, SCCR (UL/CSA)
600 A, Class J, max. Fuse, SCCR (UL/CSA)
50 kA, CB, SCCR (UL/CSA)
100 kA, Fuse, SCCR (UL/CSA)
AC-1/Conventional thermal current Ith
Switching capacity
1 A, 250 V DC, (UL/CSA)
P300, DC operated (UL/CSA)
Magnet system
AC operated: 0.2 x US max - 0.4 x US min, AC operated
DC operated: 0.2 x US max - 0.6 US min, DC operated
DC operated: 0.15 x US min - 0.6 US max, DC operated
180 W, Pull-in power, Coil in a cold state and 1.0 x Us
210 VA, Pull-in power, Coil in a cold state and 1.0 x Us