View larger
DILM225A/22(RDC24) 139550 Y7-139550 EATON ELECTRIC Contactor, 3p+2N/O+2N/C, 110kW/400V/AC3
DILM225A/22(RDC24)
139550
Y7-139550
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors more than 170 A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Large industrial plants deploy high-capacity devices such as the Eaton Moeller DILM225A/22(RDC24) contactor to manage massive electrical loads and heavy-duty motor drives. These robust switches ensure safe power isolation and reliable continuous operation in demanding electrical distribution environments.
Exact pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 0 V
- Rated control supply voltage DC (EF003980): 24 V
- Voltage type for actuating (EF008242): DC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Rail connection
- Rated operation current Ie at AC-1, 400 V (EF001393): 356 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 225 A
- Rated operation power at AC-3, 400 V (EF001364): 110 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 164 A
- Rated operation power at AC-4, 400 V (EF008496): 90 kW
- Rated operation power NEMA (EF011960): 111 kW
- Modular version (EF001126): No
- Width (EF000008): 140 mm
- Height (EF000040): 190 mm
- Depth (EF000049): 158 mm
More info
▲General specifications
CSA
CSA Class No.: 3211-04
IEC/EN 60947-4-1
UL 60947-4-1
UL File No.: E29096
VDE 0660
UL Category Control No.: NLDX
CSA File No.: 2389068
CSA-C22.2 No. 60947-4-1-14
IEC/EN 60947
UL
General
200 Operations/h
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
8 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
AC-3: Normal AC induction motors: starting, switch off during running
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
1 x (0.75 - 2.5) mm², Control circuit cables
1 x (0.75 - 2.5) mm², Control circuit cables
18 - 14, Control circuit cables
M3.5, Terminal screw, Control circuit cables
24 Nm, Main cable connection screw/bolt
Electrical rating
220 A at up to 525 V (Individual compensation, three-phase capacitors, open)
2016 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
1680 A, LRA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
280 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Short-circuit rating
600 A, max. CB, SCCR (UL/CSA)
700 A, max. Fuse, SCCR (UL/CSA)
100 kA, Fuse, SCCR (UL/CSA)
350 A, max. CB, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA)
600 A, Class J, max. Fuse, SCCR (UL/CSA)
50 kA, CB, SCCR (UL/CSA)
350 A, max. CB, SCCR (UL/CSA)
AC-1/Conventional thermal current Ith
Switching capacity
1 A, 250 V DC, (UL/CSA)
P300, DC operated (UL/CSA)
Magnet system
AC operated: 0.2 x US max - 0.4 x US min, AC operated
DC operated: 0.2 x US max - 0.6 US min, DC operated
DC operated: 0.15 x US min - 0.6 US max, DC operated
180 W, Pull-in power, Coil in a cold state and 1.0 x Us
180 W, Pull-in power, Coil in a cold state and 1.0 x Us