View larger
DILM1000/22(RAC500) 271990 Y7-271990 EATON ELECTRIC Contactor, 3p+2N/O+2N/C, 1000A/AC3
DILM1000/22(RAC500)
271990
Y7-271990
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors more than 170 A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Electric contactor (DILM1000/22(RAC500)) provides heavy-duty electrical switching for massive industrial motor loads and high-capacity power distribution systems. These large-scale components ensure safe circuit isolation and dependable performance in heavy manufacturing applications.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 480 V
- Rated control supply voltage AC 60 Hz (EF003979): 480 V
- Rated control supply voltage DC (EF003980): 250 V
- Voltage type for actuating (EF008242): AC/DC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Screw connection
- Operating voltage AC 50 Hz (EF008206): 250 V
- Operating voltage AC 60 Hz (EF008207): 250 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 1225 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 1000 A
- Rated operation power at AC-3, 400 V (EF001364): 560 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 800 A
- Rated operation power at AC-4, 400 V (EF008496): 450 kW
- Rated operation power NEMA (EF011960): 596 kW
- Modular version (EF001126): No
- Width (EF000008): 250 mm
More info
▲General specifications
UL
UL Category Control No.: NLDX
IEC/EN 60947-4-1
CE
VDE 0660
CSA File No.: 012528
IEC/EN 60947
CSA-C22.2 No. 60947-4-1-14
UL 60947-4-1
CSA
CSA Class No.: 3211-04
Global
5,000,000 Operations (DC operated)
200 Operations/h
1000 mechanical Operations/h (DC operated)
8 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
General
Damp heat, cyclic, to IEC 60068-2-30
5,000,000 Operations (DC operated)
200 Operations/h
1000 mechanical Operations/h (DC operated)
8 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Climatic environmental conditions
1 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Control circuit cables
18 - 14, Control circuit cables
M3.5, Terminal screw, Control circuit cables
35 Nm, Main cable connection screw/bolt
Terminal capacities
265 A at 690 V (Individual compensation, three-phase capacitors, open)
6000 A, LRA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
1200 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
1200 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Electrical rating
1200 A, max. CB, SCCR (UL/CSA)
2000 A, max. Fuse, SCCR (UL/CSA)
2000 A, max. Fuse, SCCR (UL/CSA)
1200 A, max. CB, SCCR (UL/CSA)
85 kA, CB, SCCR (UL/CSA)
85 kA, CB, SCCR (UL/CSA)
85 kA, Fuse, SCCR (UL/CSA)
2000 A, max. Fuse, SCCR (UL/CSA)
265 A at 690 V (Individual compensation, three-phase capacitors, open)
6000 A, LRA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
1200 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
1200 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Short-circuit rating
Conventional thermal current Ith
1 A, 250 V DC, (UL/CSA)
A600, AC operated (UL/CSA)
Switching capacity
Sealing - Voltage interruptions (0 - 0.2 x Uc min ≤ 10 ms: Time is bridged successfully
Sealing - Pick-up phase (0 - 0.7 x Uc min: Contactor does not switch on
Sealing - Pick-up phase (0.7 x Uc min - 1.15 x Uc max): Contactor switches on with certainty
Sealing - Voltage drops (0.2 - 0.6 x Uc min ≤12 ms: Time is bridged successfully
Sealing - Voltage drops (0.6 - 0.7 x Uc min: Contactor remains switched on
Sealing - Voltage interruptions 0 - 0.2 x Uc min) > 10 ms: Drop-out of the contactor
Sealing - Voltage drops (0.2 - 0.6 x Uc min) > 12 ms: Drop-out of the contactor
AC operated: 0.2 x US max - 0.6 x US min, AC operated
0.7 - 1.15 V DC x Us
800 VA, Pull-in power, Coil in a cold state and 1.0 x Us
800 VA, Pull-in power, Coil in a cold state and 1.0 x Us
12.4 W, Coil in a cold state and 1.0 x Us
28.8 VA, Coil in a cold state and 1.0 x Us
Magnet system
800 VA, Pull-in power, Coil in a cold state and 1.0 x Us
800 VA, Pull-in power, Coil in a cold state and 1.0 x Us
12.4 W, Coil in a cold state and 1.0 x Us
28.8 VA, Coil in a cold state and 1.0 x Us