View larger
DILM9-10(208V60HZ) 276684 Y7-276684 EATON ELECTRIC Contactor, 3p+1N/O, 4kW/400V/AC3
DILM9-10(208V60HZ)
276684
Y7-276684
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The DILM9-10(208V60HZ) 276684 Y7-276684 EATON ELECTRIC Contactor, 3p+1N/O, 4kW/400V/AC3 is a robust switching component utilized for managing electrical motors, lighting systems, and power distribution grids. Its primary function is to safely handle high current loads within automation panels. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 208 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Screw connection
- Operating voltage AC 50 Hz (EF008206): 24 V
- Operating voltage AC 60 Hz (EF008207): 24 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 22 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 9 A
- Rated operation power at AC-3, 400 V (EF001364): 4 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 6 A
- Rated operation power at AC-4, 400 V (EF008496): 2.5 kW
- Rated operation power NEMA (EF011960): 3.7 kW
- Modular version (EF001126): No
- Width (EF000008): 45 mm
More info
▲General specifications
CSA-C22.2 No. 14-05
UL File No.: E29096
UL 508
VDE 0660
UL
CSA File No.: 012528
IEC/EN 60947
IEC/EN 60947-4-1
UL Category Control No.: NLDX
CSA Class No.: 2411-03, 3211-04
CSA
Features & Functions
General
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Ambient conditions, mechanical
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
3.4 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
3.4 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
5.7 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Electro Magnetic Compatibility
Terminal capacities
2 x (0.75 - 2.5) mm²
1 x (0.75 - 2.5) mm²
1 x (0.75 - 4) mm²
2, Terminal screw, Pozidriv screwdriver
Electrical Rating
Short-circuit rating
60 A, max. CB, SCCR (UL/CSA)
45 A, max. Fuse, SCCR (UL/CSA)
16 A, max. CB, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA)
30/100 kA, Fuse, SCCR (UL/CSA)
25 A, Class RK5/20 A, Class J, max. Fuse, SCCR (UL/CSA)
Conventional thermal current
Switching capacity
10 A, 600 V AC, (UL/CSA)
A600, AC operated (UL/CSA)
Switching time
Magnet system
3.4 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
4.4 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Motor Rating
Communication
Contacts
Safety
400 V AC, Between coil and contacts, According to EN 61140
Special purpose ratings
18 A (600V 60Hz 3phase, 347V 60Hz 1phase)
54 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
2 HP, 200 V 60 Hz 3-ph, (UL/CSA)
2 HP, 240 V 60 Hz 3-ph, (UL/CSA)
5 HP, 600 V 60 Hz 3-ph, (UL/CSA)
7.8 A, 200 V 60 Hz 3-ph, (UL/CSA)
3 HP, 480 V 60 Hz 3-ph, (UL/CSA)
4.8 A, 480 V 60 Hz 3-ph, (UL/CSA)
6.1 A, 600 V 60 Hz 3-ph, (UL/CSA)
60 A, LRA 600 V 60 Hz 3phase; (CSA)
60 A, LRA 480 V 60 Hz 3phase; (CSA)
10 A, FLA 480 V 60 Hz 3phase; (CSA)
18 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
14 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)