View larger
DILEM-10-G(24VDC) 010213 Y7-10213 EATON ELECTRIC Contactor, 3p+1N/O, 4kW/400V/AC3
DILEM-10-G(24VDC)
DILEM-10-G(24VDC)
Y7-10213
EATON - MOELLER
1 unit
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller compact contactor provides efficient switching functionality for smaller industrial loads, auxiliary circuits, and automated machinery controls. The DILEM-10-G(24VDC) unit operates reliably within confined electrical enclosures.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz: 0 V
- Rated control supply voltage AC 60 Hz: 0 V
- Rated control supply voltage DC: 24 V
- Voltage type for actuating: DC
- Number of normally closed contacts as main contact: 0
- Number of normally open contacts as main contact: 3
- Type of electrical connection of main circuit: Screw connection
- Operating voltage AC 50 Hz: 24 V
- Operating voltage AC 60 Hz: 24 V
- Rated operation current Ie at AC-1, 400 V: 22 A
- Rated operation current Ie at AC-3, 400 V: 9 A
- Rated operation power at AC-3, 400 V: 4 kW
- Rated operation current Ie at AC-4, 400 V: 6.6 A
- Rated operation power at AC-4, 400 V: 3 kW
- Rated operation power NEMA: 3.7 kW
- Number of auxiliary contacts as normally open contact: 1
More info
▲General specifications
| Product Name | Eaton Moeller® series DILEM Mini contactor |
| Catalog Number | 010213 |
| Model Code | DILEM-10-G(24VDC) |
| EAN | 4015080102137 |
| Product Length/Depth | 54 mm |
| Product Height | 58 mm |
| Product Width | 45 mm |
| Product Weight | 0.206 kg |
| Certifications | UL 508 UL Category Control No.: NLDX IEC/EN 60947-4-1 UL File No.: E29096 CSA File No.: 012528 CSA CSA-C22.2 No. 14-05 IEC/EN 60947 CE VDE 0660 CSA Class No.: 3211-04 UL |
| Catalog Notes | Also tested according to AC-3e. |
Features & Functions
| Features | Positive operating contacts to EN 60947-5-1 appendix L, including auxiliary contact module |
| Fitted with: | Auxiliary contact |
| Number of poles | Three-pole |
General
| Application | Mini Contactors for Motors and Resistive Loads |
| Lifespan, mechanical | 20,000,000 Operations 200,000 Operations (at 240 V, AC-15) 150,000 Operations (at 240 V, DC, L/R = 50 ms: 2 contacts in series 0.5 A) |
| Mounting position | As required (except vertical with terminals A1/A2 at the bottom) |
| Operating frequency | 9000 mechanical Operations/h |
| Overvoltage category | III |
| Pollution degree | 3 |
| Product category | Contactors |
| Protection | Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274) |
| Rated impulse withstand voltage (Uimp) | 6000 V AC |
| Shock resistance | 10 g, N/O main contact, Basic unit without auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 20 g, N/O auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 8 g, N/O auxiliary contact, Basic unit without auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 10 g, N/O main contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 20 g, N/C auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
| Suitable for | Also motors with efficiency class IE3 |
| Utilization category | AC-3: Normal AC induction motors: starting, switch off during running AC-4: Normal AC induction motors: starting, plugging, reversing, inching AC-1: Non-inductive or slightly inductive loads, resistance furnaces |
| Voltage type | DC |
Climatic environmental conditions
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature - max | 50 °C |
| Ambient operating temperature (enclosed) - min | -25 °C |
| Ambient operating temperature (enclosed) - max | 40 °C |
| Ambient storage temperature - min | -40 °C |
| Ambient storage temperature - max | 80 °C |
| Climatic proofing | Damp heat, cyclic, to IEC 60068-2-30 Damp heat, constant, to IEC 60068-2-78 |
Terminal capacities
| Terminal capacity (flexible with ferrule) | 1 x (0.75 - 1.5) mm² 2 x (0.75 - 1.5) mm² |
| Terminal capacity (solid) | 2 x (0.75 - 2.5) mm² 1 x (0.75 - 2.5) mm² |
| Terminal capacity (solid/stranded AWG) | 18 - 14 |
| Stripping length (main cable) | 8 mm |
| Screwdriver size | 0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver 2, Terminal screw, Pozidriv screwdriver |
| Tightening torque | 1.2 Nm, Screw terminals |
Electrical rating
| Rated breaking capacity at 220/230 V | 90 A |
| Rated breaking capacity at 380/400 V | 90 A |
| Rated breaking capacity at 500 V | 64 A |
| Rated operational power at AC-3, 240 V, 50 Hz | 2.5 kW |
| Rated operational power at AC-3, 380/400 V, 50 Hz | 4 kW |
| Rated operational power at AC-3, 415 V, 50 Hz | 4.3 kW |
| Rated breaking capacity at 660/690 V | 42 A |
| Rated making capacity up to 440 V (cos phi to IEC/EN 60947) | 110 A |
| Rated operational power at AC-4, 220/230 V, 50 Hz | 1.5 kW |
| Rated operational power at AC-4, 240 V, 50 Hz | 1.8 kW |
| Rated operational power at AC-4, 415 V, 50 Hz | 3.1 kW |
| Rated operational power at AC-4, 440 V, 50 Hz | 3.3 kW |
| Rated operational power at AC-4, 500 V, 50 Hz | 3 kW |
| Rated operational power at AC-4, 660/690 V, 50 Hz | 3 kW |
| Rated operational voltage (Ue) at AC - max | 690 V |
| Rated insulation voltage (Ui) | 690 V |
| Rated operational current (Ie) | 2.5 A at 60 V, DC L/R ≤ 15 ms (with 2 contacts in series) 1.5 A at 100 V, DC L/R ≤ 15 ms (with 3 contacts in series) 2.5 A at 24 V, DC L/R ≤ 15 ms (with 1 contact in series) 0.5 A at 220 V, DC L/R ≤ 15 ms (with 3 contacts in series) |
| Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V | 22 A |
| Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V | 6 A |
| Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V | 3 A |
| Rated operational current (Ie) at AC-15, 500 V | 1.5 A |
| Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V | 9 A |
| Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V | 9 A |
| Rated operational current (Ie) at AC-3, 440 V | 9 A |
| Rated operational current (Ie) at AC-3, 500 V | 6.4 A |
| Rated operational current (Ie) at AC-3, 660 V, 690 V | 4.8 A |
| Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V | 6.6 A |
| Rated operational current (Ie) at AC-4, 440 V | 6.6 A |
| Rated operational current (Ie) at AC-4, 500 V | 5 A |
| Rated operational current (Ie) at AC-4, 660 V, 690 V | 3.4 A |
| Rated operational current (Ie) at DC-1, 110 V | 20 A |
| Rated operational current (Ie) at DC-1, 12 V | 20 A |
| Rated operational current (Ie) at DC-1, 220 V | 20 A |
| Rated operational current (Ie) at DC-1, 24 V | 20 A |
| Rated operational current (Ie) at DC-1, 60 V | 20 A |
| Safe isolation | 300 V AC, Between the contacts, According to EN 61140 300 V AC, Between coil and auxiliary contacts, According to EN 61140 300 V AC, Between auxiliary contacts, According to EN 61140 300 V AC, Between coil and contacts, According to EN 61140 |
Short-circuit rating
| Short-circuit current rating (basic rating) | 5 kA, SCCR (UL/CSA) 45 A, max. Fuse, SCCR (UL/CSA) |
| Short-circuit protection | 6 A gG/gL, Max. Fuse 500V, Auxiliary contacts, Short-circuit rating without welding 10 A fast, Max. Fuse 500V, Auxiliary contacts, Short-circuit rating without welding PKZM0-4, Maximum overcurrent protective device, Short-circuit protection only, Auxiliary contacts, Short-circuit rating without welding |
| Short-circuit protection rating (type 1 coordination) at 500 V | 20 A gG/gL |
| Short-circuit protection rating (type 2 coordination) at 500 V | 10 A gG/gL |
Conventional thermal current Ith
| Conventional thermal current Ith (1-pole, enclosed) | 40 A |
| Conventional thermal current Ith (3-pole, enclosed) | 16 A |
| Conventional thermal current Ith at 55°C (3-pole, open) | 19 A |
| Conventional thermal current Ith of auxiliary contacts (1-pole, open) | 10 A |
| Conventional thermal current Ith of main contacts (1-pole, open) | 50 A |
Switching capacity
| Switching capacity (main contacts, general use) | 15 A, Maximum motor rating (UL/CSA) |
| Switching capacity (auxiliary contacts, general use) | 0.5 A, 250 V DC, (UL/CSA) 10 A, 600 V AC, (UL/CSA) |
| Switching capacity (auxiliary contacts, pilot duty) | P300, DC operated (UL/CSA) A600, AC operated (UL/CSA) |
Magnet system
| Arcing time | 12 ms at 690 V AC |
| Changeover time | 40 - 50 ms |
| Duty factor | 100 % |
| Pick-up voltage | 0.8 - 1.1 V DC x Uc |
| Power consumption | Smoothed DC voltage or three-phase bridge rectifier 2.3 VA/W at DC (Pick-up/Sealing power) |
| Rated control supply voltage (Us) at AC, 50 Hz - min | 0 V |
| Rated control supply voltage (Us) at AC, 50 Hz - max | 0 V |
| Rated control supply voltage (Us) at AC, 60 Hz - min | 0 V |
| Rated control supply voltage (Us) at AC, 60 Hz - max | 0 V |
| Rated control supply voltage (Us) at DC - min | 24 V |
| Rated control supply voltage (Us) at DC - max | 24 V |
| Switching time (AC operated, N/O, with auxiliary contact module, closing delay) | 70 ms |
| Switching time (DC operated, make contacts, closing delay) - min | 26 ms |
| Switching time (DC operated, make contacts, closing delay) - max | 35 ms |
| Switching time (DC operated, make contacts, opening delay) - min | 15 ms |
| Switching time (DC operated, make contacts, opening delay) - max | 25 ms |
Motor rating
| Assigned motor power at 115/120 V, 60 Hz, 1-phase | 0.5 HP |
| Assigned motor power at 200/208 V, 60 Hz, 3-phase | 2 HP |
| Assigned motor power at 230/240 V, 60 Hz, 1-phase | 1.5 HP |
| Assigned motor power at 230/240 V, 60 Hz, 3-phase | 3 HP |
| Assigned motor power at 460/480 V, 60 Hz, 3-phase | 5 HP |
| Assigned motor power at 575/600 V, 60 Hz, 3-phase | 5 HP |
Contacts
| Control circuit reliability | < 2 λ, < 1 failure at 100,000,000 Operations (at Uₑ = 24 V DC, Umin = 17 V, Imin = 5.4 mA) |
| Number of auxiliary contacts (normally closed contacts) | 0 |
| Number of auxiliary contacts (normally open contacts) | 1 |
Design verification
| Equipment heat dissipation, current-dependent Pvid | 0.9 W |
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 0.3 W |
| Rated operational current for specified heat dissipation (In) | 9 A |
| Static heat dissipation, non-current-dependent Pvs | 2.3 W |
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |