View larger
DILM7-10(42V50HZ,48V60HZ) 276546 Y7-276546 EATON ELECTRIC Contactor, 3p + 1N / O, 3kW / 400V / AC3
DILM7-10(42V50HZ,48V60HZ)
276546
Y7-276546
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The DILM7-10(42V50HZ,48V60HZ) Eaton Moeller power contactor is widely applied in industrial environments to facilitate remote switching for electric motors, pumps, and automated assembly equipment.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 42 V
- Rated control supply voltage AC 60 Hz (EF003979): 48 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Screw connection
- Operating voltage AC 50 Hz (EF008206): 24 V
- Operating voltage AC 60 Hz (EF008207): 24 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 22 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 7 A
- Rated operation power at AC-3, 400 V (EF001364): 3 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 5 A
- Rated operation power at AC-4, 400 V (EF008496): 2.2 kW
- Rated operation power NEMA (EF011960): 2.2 kW
- Modular version (EF001126): No
- Width (EF000008): 45 mm
More info
▲General specifications
VDE 0660
UL 60947-4-1
UL
CSA
IEC/EN 60947
IEC/EN 60947-4-1
CSA Class No.: 2411-03, 3211-04
CE
UL Category Control No.: NLDX
CSA-C22.2 No. 60947-4-1-14
UL File No.: E29096
Features & Functions
General
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-3: Normal AC induction motors: starting, switch off during running
Ambient conditions, mechanical
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
3.4 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
5.7 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
3.4 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Electro Magnetic Compatibility
Terminal capacities
2 x (0.75 - 2,5) mm²
2 x (0.75 - 2.5) mm²
2 x (0.75 - 2.5) mm²
0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver
Electrical Rating
Short-circuit rating
60 A, max. CB, SCCR (UL/CSA)
5 kA, SCCR (UL/CSA)
25 A, Class RK5/ 20 A Class J, max. Fuse, SCCR (UL/CSA)
30/100 kA, Fuse, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA)
30/100 kA, Fuse, SCCR (UL/CSA)
Conventional thermal current
Switching capacity
1 A, 250 V DC, (UL/CSA)
A600, AC operated (UL/CSA)
Switching time
Magnet system
1.4 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
1.4 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Motor Rating
Communication
Contacts
Safety
400 V AC, Between coil and contacts, According to EN 61140
Special purpose ratings
12 A (480V 60Hz 3phase, 277V 60Hz 1phase)
7 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
0.75 HP, 200 V 60 Hz 3-ph, (UL/CSA)
6 A, 240 V 60 Hz 3-ph, (UL/CSA)
3.9 A, 600 V 60 Hz 3-ph, (UL/CSA)
3.7 A, 200 V 60 Hz 3-ph, (UL/CSA)
2 HP, 480 V 60 Hz 3-ph, (UL/CSA)
3.4 A, 480 V 60 Hz 3-ph, (UL/CSA)
3 HP, 600 V 60 Hz 3-ph, (UL/CSA)
10 A, FLA 480 V 60 Hz 3phase; (CSA)
10 A, FLA 600 V 60 Hz 3phase; (CSA)
60 A, LRA 600 V 60 Hz 3phase; (CSA)
12 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
14 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)