Equipped with spring clamp connections, the Eaton Moeller DILEEM-10-C(230V50/60HZ) contactor provides efficient and secure circuit switching for compact industrial automation setups. Miniature contactors are regularly selected by panel builders to optimize space while maintaining dependable motor and auxiliary control. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 230 V
- Rated control supply voltage AC 60 Hz (EF003979): 230 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Spring clamp connection
- Operating voltage AC 50 Hz (EF008206): 24 V
- Operating voltage AC 60 Hz (EF008207): 24 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 22 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 6.6 A
- Rated operation power at AC-3, 400 V (EF001364): 3 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 5 A
- Rated operation power at AC-4, 400 V (EF008496): 2.2 kW
- Rated operation power NEMA (EF011960): 2.2 kW
- Modular version (EF001126): No
- Width (EF000008): 45 mm
More info
▲General specifications
UL File No.: E29096
IEC/EN 60947
IEC/EN 60947-4-1
UL Category Control No.: NLDX
CE
CSA Class No.: 3211-04
UL
CSA
CSA File No.: 012528
CSA-C22.2 No. 14-05
VDE 0660
Features & Functions
General
150,000 Operations (at 240 V, DC, L/R = 50 ms: 2 contacts in series 0.5 A)
200,000 Operations (at 240 V, AC-15)
10,000,000 Operations
20 g, N/C auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
8 g, N/O auxiliary contact, Basic unit without auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
20 g, N/O auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-3: Normal AC induction motors: starting, switch off during running
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
1 x (1 - 2.5) mm²
Electrical rating
2.5 A at 24 V, DC L/R ≤ 15 ms (with 1 contact in series)
2.5 A at 60 V, DC L/R ≤ 15 ms (with 2 contacts in series)
1.5 A at 100 V, DC L/R ≤ 15 ms (with 3 contacts in series)
300 V AC, Between the contacts, According to EN 61140
300 V AC, Between auxiliary contacts, According to EN 61140
300 V AC, Between coil and auxiliary contacts, According to EN 61140
Short-circuit rating
5 kA, SCCR (UL/CSA)
10 A fast, Max. Fuse 500V, Auxiliary contacts, Short-circuit rating without welding
PKZM0-4, Maximum overcurrent protective device, Short-circuit protection only, Auxiliary contacts, Short-circuit rating without welding
Conventional thermal current Ith
Switching capacity
0.5 A, 250 V DC, (UL/CSA)
A600, AC operated (UL/CSA)
Magnet system
30 VA, AC, Dual-frequency coil at 50 Hz
29 VA, AC, Dual-frequency coil at 60 Hz
1.8 W, Coil in a cold state and 1.0 x Us
1.8 W, Coil in a cold state and 1.0 x Us
3.9 VA, AC, Dual-frequency coil at 60 Hz
1.8 W, AC, Dual-frequency coil at 60 Hz