View larger
DILM32-10(230V50/60HZ) 277268 Y7-277268 EATON ELECTRIC Contactor, 3p+1N/O, 15kW/400V/AC3
DILM32-10(230V50/60HZ)
277268
Y7-277268
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller part number DILM32-10(230V50/60HZ) is a DILM32-10(230V50/60HZ) 277268 Y7-277268 EATON ELECTRIC Contactor, 3p+1N/O, 15kW/400V/AC3 engineered for high-frequency switching operations in automated manufacturing lines. Industrial contactors provide dependable remote power switching for electric motors, pumps, and ventilation equipment within diverse production environments. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Manufacturer: Eaton Moeller
- Manufacturer part number: DILM32-10(230V50/60HZ)
- Catalogue code: 277268
- Catalogue title: DILM32-10(230V50/60HZ) 277268 Y7-277268 EATON ELECTRIC Contactor, 3p+1N/O, 15kW/400V/AC3
More info
▲General specifications
CSA Std. C22.2 No. 14-05
EN 60947-4-1
IEC 60947-4-1
VDE
UL Category Control No.: NLDX
CSA
VDE 0660
CE
IEC/EN 60947-4-1
UL 60947-4-1
UL File No.: E29096
CSA Class No.: 2411-03, 3211-04
IEC/EN 60947
CSA-C22.2 No. 60947-4-1-14
CSA File No.: 012528
UL
Features & Functions
General
7,000,000 Operations (Coil 50/60 Hz)
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Ambient conditions, mechanical
5.3 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
3.5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Electro Magnetic Compatibility
Terminal capacities
1 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Control circuit cables
1 x (0.75 - 16) mm², Main cables
1 x (0.75 - 16) mm², Main cables
2 x (0.75 - 10) mm², Main cables
1 x (0.75 - 4) mm², Control circuit cables
18 - 14, Control circuit cables
M5, Terminal screw, Main cables
0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver
3.2 Nm, Screw terminals, Main cables
Electrical Rating
Short-circuit rating
5 kA, SCCR (UL/CSA)
125 A, max. CB, SCCR (UL/CSA)
125/70 A, Class J, max. Fuse, SCCR (UL/CSA)
50/32 A, max. CB, SCCR (UL/CSA)
10/100 kA, Fuse, SCCR (UL/CSA)
10/100 kA, Fuse, SCCR (UL/CSA)
125/125 A, Class J, max. Fuse, SCCR (UL/CSA)
10/22 kA, CB, SCCR (UL/CSA)
Conventional thermal current
Switching capacity
1 A, 250 V DC, (UL/CSA)
A600, AC operated (UL/CSA)
Switching time
Magnet system
62 VA, Dual-frequency coil in a cold state and 1.0 x Us
58 VA, Dual-frequency coil in a cold state and 1.0 x Us
6.5 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
9.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Motor Rating
Communication
Contacts
Safety
440 V AC, Between the contacts, According to EN 61140
Special purpose ratings
40 A (480V 60Hz 3phase, 277V 60Hz 1phase)
192 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
22 A, 600 V 60 Hz 3-ph, (UL/CSA)
25.3 A, 200 V 60 Hz 3-ph, (UL/CSA)
27 A, 480 V 60 Hz 3-ph, (UL/CSA)
7.5 HP, 240 V 60 Hz 3-ph, (UL/CSA)
22 A, 240 V 60 Hz 3-ph, (UL/CSA)
20 HP, 480 V 60 Hz 3-ph, (UL/CSA)
20 HP, 600 V 60 Hz 3-ph, (UL/CSA)
180 A, LRA 600 V 60 Hz 3phase; (CSA)
40 A, FLA 480 V 60 Hz 3phase; (CSA)
30 A, FLA 600 V 60 Hz 3phase; (CSA)
40 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
40 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)