View larger
DILM32-10(110V50HZ,120V60HZ) 277257 Y7-277257 EATON ELECTRIC Contactor, 3p + 1N / O, 15kW / 400V / AC3
DILM32-10(110V50HZ,120V60HZ)
277257
Y7-277257
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller power contactor serves as a crucial electromechanical switching device in industrial machinery, allowing remote control of high-amperage motor loads and power feeds. These components are built to endure millions of switching cycles in automated environments. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 110 V
- Rated control supply voltage AC 60 Hz (EF003979): 120 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Screw connection
- Operating voltage AC 50 Hz (EF008206): 24 V
- Operating voltage AC 60 Hz (EF008207): 24 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 45 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 32 A
- Rated operation power at AC-3, 400 V (EF001364): 15 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 15 A
- Rated operation power at AC-4, 400 V (EF008496): 7 kW
- Rated operation power NEMA (EF011960): 14.9 kW
- Modular version (EF001126): No
- Width (EF000008): 45 mm
More info
▲General specifications
IEC/EN 60947-4-1
UL Category Control No.: NLDX
UL
IEC/EN 60947
UL 60947-4-1
CSA Class No.: 2411-03, 3211-04
VDE 0660
CSA
UL File No.: E29096
CSA File No.: 012528
CSA-C22.2 No. 60947-4-1-14
Features & Functions
General
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Ambient conditions, mechanical
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
3.5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
6.9 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
5.3 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Electro Magnetic Compatibility
Terminal capacities
1 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Control circuit cables
1 x (0.75 - 16) mm², Main cables
2 x (0.75 - 10) mm², Main cables
1 x (0.75 - 4) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Control circuit cables
Single 18 - 6, double 18 - 8, Main cables
M3.5, Terminal screw, Control circuit cables
2, Terminal screw, Pozidriv screwdriver
3.2 Nm, Screw terminals, Main cables
Electrical Rating
Short-circuit rating
125 A, max. Fuse, SCCR (UL/CSA)
5 kA, SCCR (UL/CSA)
10/100 kA, Fuse, SCCR (UL/CSA)
50/32 A, max. CB, SCCR (UL/CSA)
125/70 A, Class J, max. Fuse, SCCR (UL/CSA)
10/22 kA, CB, SCCR (UL/CSA)
50/32 A, max. CB, SCCR (UL/CSA)
10/100 kA, Fuse, SCCR (UL/CSA)
Conventional thermal current
Switching capacity
1 A, 250 V DC, (UL/CSA)
P300, DC operated (UL/CSA)
Switching time
Magnet system
2.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
8.7 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Motor Rating
Communication
Contacts
Safety
440 V AC, Between coil and contacts, According to EN 61140
Special purpose ratings
40 A (600V 60Hz 3phase, 347V 60Hz 1phase)
192 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
25.3 A, 200 V 60 Hz 3-ph, (UL/CSA)
20 HP, 480 V 60 Hz 3-ph, (UL/CSA)
22 A, 240 V 60 Hz 3-ph, (UL/CSA)
20 HP, 600 V 60 Hz 3-ph, (UL/CSA)
7.5 HP, 200 V 60 Hz 3-ph, (UL/CSA)
27 A, 480 V 60 Hz 3-ph, (UL/CSA)
7.5 HP, 240 V 60 Hz 3-ph, (UL/CSA)
40 A, FLA 480 V 60 Hz 3phase; (CSA)
30 A, FLA 600 V 60 Hz 3phase; (CSA)
180 A, LRA 600 V 60 Hz 3phase; (CSA)
40 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
40 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)