Featuring reliable DC operation, the Eaton Moeller DILEM12-01-G(24VDC) mini contactor offers compact power switching for sophisticated control cabinets. Miniature contactors are widely deployed to manage auxiliary motor loads and smaller actuators in confined spaces. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Manufacturer: Eaton Moeller
- Manufacturer part number: DILEM12-01-G(24VDC)
- Catalogue code: 127137
More info
▲General specifications
UL 508
CSA Class No.: 3211-04
UL File No.: E29096
VDE 0660
CSA File No.: 012528
CE
CSA
CSA-C22.2 No. 14-05
IEC/EN 60947
UL Category Control No.: NLDX
IEC/EN 60947-4-1
Features & Functions
General
200,000 Operations (at 240 V, AC-15)
5,000,000 Operations
20 g, N/O auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
20 g, N/C auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/C auxiliary contact, Basic unit without auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Basic unit without auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-3: Normal AC induction motors: starting, switch off during running
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
1 x (0.75 - 1.5) mm²
2 x (0.75 - 2.5) mm²
0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver
Electrical rating
0.5 A at 220 V, DC L/R ≤ 15 ms (with 3 contacts in series)
1.5 A at 100 V, DC L/R ≤ 15 ms (with 3 contacts in series)
2.5 A at 24 V, DC L/R ≤ 15 ms (with 1 contact in series)
300 V AC, Between coil and contacts, According to EN 61140
300 V AC, Between auxiliary contacts, According to EN 61140
300 V AC, Between coil and auxiliary contacts, According to EN 61140
Short-circuit rating
45 A, max. Fuse, SCCR (UL/CSA)
PKZM0-4, Maximum overcurrent protective device, Short-circuit protection only, Auxiliary contacts, Short-circuit rating without welding
6 A gG/gL, Max. Fuse 500V, Auxiliary contacts, Short-circuit rating without welding
Conventional thermal current Ith
Switching capacity
10 A, 600 V AC, (UL/CSA)
A600, AC operated (UL/CSA)
Magnet system
2.3 VA/W at DC (Pick-up/Sealing power)