View larger
DILEM12-01(230V50HZ,240V60HZ) 127091 Y7-127091 EATON ELECTRIC 127091 DILEM12-01(230V50HZ,240V60HZ)
DILEM12-01(230V50HZ,240V60HZ)
127091
Y7-127091
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
DILEM12-01(230V50HZ,240V60HZ) produced by Eaton Moeller is a specialized mini contactor engineered for reliable circuit control and motor switching in compact industrial control panels. It delivers robust performance for smaller automated drives where panel space is at a premium. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Manufacturer: Eaton Moeller
- Part Number: DILEM12-01(230V50HZ,240V60HZ)
- Pole Count: 3 pole
- Rating: 5.5 kW / 400 V
- Aux Contacts: 1 NC
More info
▲General specifications
CSA
CE
CSA-C22.2 No. 14-05
UL Category Control No.: NLDX
CSA File No.: 012528
IEC/EN 60947-4-1
UL 508
UL File No.: E29096
CSA Class No.: 3211-04
VDE 0660
UL
Features & Functions
General
5,000,000 Operations (Coil 50/60 Hz)
5,000,000 Operations
200,000 Operations (at 240 V, AC-15)
20 g, N/C auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/C auxiliary contact, Basic unit without auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Basic unit without auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
1 x (0.75 - 1.5) mm²
1 x (0.75 - 2.5) mm²
2, Terminal screw, Pozidriv screwdriver
Electrical rating
1.5 A at 100 V, DC L/R ≤ 15 ms (with 3 contacts in series)
2.5 A at 60 V, DC L/R ≤ 15 ms (with 2 contacts in series)
0.5 A at 220 V, DC L/R ≤ 15 ms (with 3 contacts in series)
300 V AC, Between coil and contacts, According to EN 61140
300 V AC, Between coil and auxiliary contacts, According to EN 61140
300 V AC, Between auxiliary contacts, According to EN 61140
Short-circuit rating
5 kA, SCCR (UL/CSA)
6 A gG/gL, Max. Fuse 500V, Auxiliary contacts, Short-circuit rating without welding
PKZM0-4, Maximum overcurrent protective device, Short-circuit protection only, Auxiliary contacts, Short-circuit rating without welding
Conventional thermal current Ith
Switching capacity
10 A, 600 V AC, (UL/CSA)
A600, AC operated (UL/CSA)
Magnet system
0.8 - 1.1 V AC x Uc (voltage tolerance - single-voltage coil 50 Hz and dual-voltage coil 50 Hz, 60 Hz)
25 VA, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz
25 VA, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz
4.6 VA, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz