View larger
DILEM-01(230V50/60HZ) 051114 Y7-51114 EATON ELECTRIC Contactor, 3p+1N/C, 4kW/400V/AC3
DILEM-01(230V50/60HZ)
051114
Y7-51114
EATON - MOELLER
5 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller part number DILEM-01(230V50/60HZ) is an Eaton Electric Contactor designed for efficient motor control and auxiliary switching in compact industrial enclosures. Standard contactors enable automation systems to govern high-power loads securely using low-voltage control signals. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 230 V
- Rated control supply voltage AC 60 Hz (EF003979): 230 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Screw connection
- Operating voltage AC 50 Hz (EF008206): 24 V
- Operating voltage AC 60 Hz (EF008207): 24 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 22 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 9 A
- Rated operation power at AC-3, 400 V (EF001364): 4 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 6.6 A
- Rated operation power at AC-4, 400 V (EF008496): 3 kW
- Rated operation power NEMA (EF011960): 3.7 kW
- Modular version (EF001126): No
- Width (EF000008): 45 mm
More info
▲General specifications
IEC/EN 60947
VDE 0660
UL 508
UL File No.: E29096
CE
IEC/EN 60947-4-1
CSA
CSA Class No.: 3211-04
CSA-C22.2 No. 14-05
CSA File No.: 012528
UL Category Control No.: NLDX
Features & Functions
General
7,000,000 Operations (Coil 50/60 Hz)
150,000 Operations (at 240 V, DC, L/R = 50 ms: 2 contacts in series 0.5 A)
200,000 Operations (at 240 V, AC-15)
20 g, N/C auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/C auxiliary contact, Basic unit without auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Basic unit without auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-3: Normal AC induction motors: starting, switch off during running
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
2 x (0.75 - 1.5) mm²
1 x (0.75 - 2.5) mm²
0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver
Electrical rating
2.5 A at 24 V, DC L/R ≤ 15 ms (with 1 contact in series)
1.5 A at 100 V, DC L/R ≤ 15 ms (with 3 contacts in series)
2.5 A at 60 V, DC L/R ≤ 15 ms (with 2 contacts in series)
300 V AC, Between coil and contacts, According to EN 61140
300 V AC, Between coil and auxiliary contacts, According to EN 61140
300 V AC, Between auxiliary contacts, According to EN 61140
Short-circuit rating
45 A, max. Fuse, SCCR (UL/CSA)
PKZM0-4, Maximum overcurrent protective device, Short-circuit protection only, Auxiliary contacts, Short-circuit rating without welding
6 A gG/gL, Max. Fuse 500V, Auxiliary contacts, Short-circuit rating without welding
Conventional thermal current Ith
Switching capacity
0.5 A, 250 V DC, (UL/CSA)
A600, AC operated (UL/CSA)
Magnet system
30 VA, AC, Dual-frequency coil at 50 Hz
24 W, AC, Dual-frequency coil at 60 Hz
1.8 W, Coil in a cold state and 1.0 x Us
5.4 VA, Coil in a cold state and 1.0 x Us
1.8 W, Coil in a cold state and 1.0 x Us
1.8 W, AC, Dual-frequency coil at 60 Hz