| Product Name | Eaton Moeller® series DILEM Mini contactor |
| Catalog Number | 010343 |
| Model Code | DILEM-01-G(24VDC) |
| EAN | 4015080103431 |
| Product Length/Depth | 54 mm |
| Product Height | 58 mm |
| Product Width | 45 mm |
| Product Weight | 0.206 kg |
| Certifications | CSA-C22.2 No. 14-05 UL File No.: E29096 CSA Class No.: 3211-04 UL IEC/EN 60947-4-1 IEC/EN 60947 CSA File No.: 012528 VDE 0660 UL 508 UL Category Control No.: NLDX CSA CE |
| Catalog Notes | Also tested according to AC-3e. |
| Features | Positive operating contacts to EN 60947-5-1 appendix L, including auxiliary contact module |
| Fitted with: | Auxiliary contact |
| Number of poles | Three-pole |
| Application | Mini Contactors for Motors and Resistive Loads |
| Lifespan, mechanical | 20,000,000 Operations 200,000 Operations (at 240 V, AC-15) 150,000 Operations (at 240 V, DC, L/R = 50 ms: 2 contacts in series 0.5 A) |
| Mounting position | As required (except vertical with terminals A1/A2 at the bottom) |
| Operating frequency | 9000 mechanical Operations/h |
| Overvoltage category | III |
| Pollution degree | 3 |
| Product category | Contactors |
| Protection | Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274) |
| Rated impulse withstand voltage (Uimp) | 6000 V AC |
| Shock resistance | 20 g, N/C auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 20 g, N/O auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 10 g, N/C auxiliary contact, Basic unit without auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 10 g, N/O main contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 10 g, N/O main contact, Basic unit without auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
| Suitable for | Also motors with efficiency class IE3 |
| Utilization category | AC-3: Normal AC induction motors: starting, switch off during running AC-4: Normal AC induction motors: starting, plugging, reversing, inching AC-1: Non-inductive or slightly inductive loads, resistance furnaces |
| Voltage type | DC |
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature - max | 50 °C |
| Ambient operating temperature (enclosed) - min | -25 °C |
| Ambient operating temperature (enclosed) - max | 40 °C |
| Ambient storage temperature - min | -40 °C |
| Ambient storage temperature - max | 80 °C |
| Climatic proofing | Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 |
| Terminal capacity (flexible with ferrule) | 2 x (0.75 - 1.5) mm² 1 x (0.75 - 1.5) mm² |
| Terminal capacity (solid) | 1 x (0.75 - 2.5) mm² 2 x (0.75 - 2.5) mm² |
| Terminal capacity (solid/stranded AWG) | 18 - 14 |
| Stripping length (main cable) | 8 mm |
| Screwdriver size | 0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver 2, Terminal screw, Pozidriv screwdriver |
| Tightening torque | 1.2 Nm, Screw terminals |
| Rated breaking capacity at 220/230 V | 90 A |
| Rated breaking capacity at 380/400 V | 90 A |
| Rated breaking capacity at 500 V | 64 A |
| Rated operational power at AC-3, 240 V, 50 Hz | 2.5 kW |
| Rated operational power at AC-3, 380/400 V, 50 Hz | 4 kW |
| Rated operational power at AC-3, 415 V, 50 Hz | 4.3 kW |
| Rated breaking capacity at 660/690 V | 42 A |
| Rated making capacity up to 440 V (cos phi to IEC/EN 60947) | 110 A |
| Rated operational power at AC-4, 220/230 V, 50 Hz | 1.5 kW |
| Rated operational power at AC-4, 240 V, 50 Hz | 1.8 kW |
| Rated operational power at AC-4, 415 V, 50 Hz | 3.1 kW |
| Rated operational power at AC-4, 440 V, 50 Hz | 3.3 kW |
| Rated operational power at AC-4, 500 V, 50 Hz | 3 kW |
| Rated operational power at AC-4, 660/690 V, 50 Hz | 3 kW |
| Rated operational voltage (Ue) at AC - max | 690 V |
| Rated insulation voltage (Ui) | 690 V |
| Rated operational current (Ie) | 2.5 A at 60 V, DC L/R ≤ 15 ms (with 2 contacts in series) 1.5 A at 100 V, DC L/R ≤ 15 ms (with 3 contacts in series) 0.5 A at 220 V, DC L/R ≤ 15 ms (with 3 contacts in series) 2.5 A at 24 V, DC L/R ≤ 15 ms (with 1 contact in series) |
| Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V | 22 A |
| Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V | 6 A |
| Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V | 3 A |
| Rated operational current (Ie) at AC-15, 500 V | 1.5 A |
| Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V | 9 A |
| Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V | 9 A |
| Rated operational current (Ie) at AC-3, 440 V | 9 A |
| Rated operational current (Ie) at AC-3, 500 V | 6.4 A |
| Rated operational current (Ie) at AC-3, 660 V, 690 V | 4.8 A |
| Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V | 6.6 A |
| Rated operational current (Ie) at AC-4, 440 V | 6.6 A |
| Rated operational current (Ie) at AC-4, 500 V | 5 A |
| Rated operational current (Ie) at AC-4, 660 V, 690 V | 3.4 A |
| Rated operational current (Ie) at DC-1, 110 V | 20 A |
| Rated operational current (Ie) at DC-1, 12 V | 20 A |
| Rated operational current (Ie) at DC-1, 220 V | 20 A |
| Rated operational current (Ie) at DC-1, 24 V | 20 A |
| Rated operational current (Ie) at DC-1, 60 V | 20 A |
| Safe isolation | 300 V AC, Between coil and contacts, According to EN 61140 300 V AC, Between auxiliary contacts, According to EN 61140 300 V AC, Between the contacts, According to EN 61140 300 V AC, Between coil and auxiliary contacts, According to EN 61140 |
| Short-circuit current rating (basic rating) | 45 A, max. Fuse, SCCR (UL/CSA) 5 kA, SCCR (UL/CSA) |
| Short-circuit protection | PKZM0-4, Maximum overcurrent protective device, Short-circuit protection only, Auxiliary contacts, Short-circuit rating without welding 10 A fast, Max. Fuse 500V, Auxiliary contacts, Short-circuit rating without welding 6 A gG/gL, Max. Fuse 500V, Auxiliary contacts, Short-circuit rating without welding |
| Short-circuit protection rating (type 1 coordination) at 500 V | 20 A gG/gL |
| Short-circuit protection rating (type 2 coordination) at 500 V | 10 A gG/gL |
| Conventional thermal current Ith (1-pole, enclosed) | 40 A |
| Conventional thermal current Ith (3-pole, enclosed) | 16 A |
| Conventional thermal current Ith at 55°C (3-pole, open) | 19 A |
| Conventional thermal current Ith of auxiliary contacts (1-pole, open) | 10 A |
| Conventional thermal current Ith of main contacts (1-pole, open) | 50 A |
| Switching capacity (main contacts, general use) | 15 A, Maximum motor rating (UL/CSA) |
| Switching capacity (auxiliary contacts, general use) | 0.5 A, 250 V DC, (UL/CSA) 10 A, 600 V AC, (UL/CSA) |
| Switching capacity (auxiliary contacts, pilot duty) | P300, DC operated (UL/CSA) A600, AC operated (UL/CSA) |
| Arcing time | 12 ms at 690 V AC |
| Changeover time | 40 - 50 ms |
| Duty factor | 100 % |
| Pick-up voltage | 0.8 - 1.1 V DC x Uc |
| Power consumption | 2.3 VA/W at DC (Pick-up/Sealing power) Smoothed DC voltage or three-phase bridge rectifier |
| Rated control supply voltage (Us) at AC, 50 Hz - min | 0 V |
| Rated control supply voltage (Us) at AC, 50 Hz - max | 0 V |
| Rated control supply voltage (Us) at AC, 60 Hz - min | 0 V |
| Rated control supply voltage (Us) at AC, 60 Hz - max | 0 V |
| Rated control supply voltage (Us) at DC - min | 24 V |
| Rated control supply voltage (Us) at DC - max | 24 V |
| Switching time (AC operated, N/O, with auxiliary contact module, closing delay) | 70 ms |
| Switching time (DC operated, make contacts, closing delay) - min | 26 ms |
| Switching time (DC operated, make contacts, closing delay) - max | 35 ms |
| Switching time (DC operated, make contacts, opening delay) - min | 15 ms |
| Switching time (DC operated, make contacts, opening delay) - max | 25 ms |
| Assigned motor power at 115/120 V, 60 Hz, 1-phase | 0.5 HP |
| Assigned motor power at 200/208 V, 60 Hz, 3-phase | 2 HP |
| Assigned motor power at 230/240 V, 60 Hz, 1-phase | 1.5 HP |
| Assigned motor power at 230/240 V, 60 Hz, 3-phase | 3 HP |
| Assigned motor power at 460/480 V, 60 Hz, 3-phase | 5 HP |
| Assigned motor power at 575/600 V, 60 Hz, 3-phase | 5 HP |
| Control circuit reliability | < 2 λ, < 1 failure at 100,000,000 Operations (at Uₑ = 24 V DC, Umin = 17 V, Imin = 5.4 mA) |
| Number of auxiliary contacts (normally closed contacts) | 1 |
| Number of auxiliary contacts (normally open contacts) | 0 |
| Equipment heat dissipation, current-dependent Pvid | 0.9 W |
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 0.3 W |
| Rated operational current for specified heat dissipation (In) | 9 A |
| Static heat dissipation, non-current-dependent Pvs | 2.3 W |
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
| Feature Name | Feature Value |
|---|---|
| Rated control supply voltage AC 50 Hz (EF003978) | 0 V |
| Rated control supply voltage AC 60 Hz (EF003979) | 0 V |
| Rated control supply voltage DC (EF003980) | 24 V |
| Voltage type for actuating (EF008242) | DC |
| Number of normally closed contacts as main contact (EF001375) | 0 |
| Number of normally open contacts as main contact (EF001374) | 3 |
| Type of electrical connection of main circuit (EF006819) | Screw connection |
| Operating voltage AC 50 Hz (EF008206) | 24 V |
| Operating voltage AC 60 Hz (EF008207) | 24 V |
| Rated operation current Ie at AC-1, 400 V (EF001393) | 22 A |
| Rated operation current Ie at AC-3, 400 V (EF001392) | 9 A |
| Rated operation power at AC-3, 400 V (EF001364) | 4 kW |
| Rated operation current Ie at AC-4, 400 V (EF008495) | 6.6 A |
| Rated operation power at AC-4, 400 V (EF008496) | 3 kW |
| Rated operation power NEMA (EF011960) | 3.7 kW |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as normally closed contact (EF001377) | 1 |
| Modular version (EF001126) | No |
| Width (EF000008) | 45 mm |
| Height (EF000040) | 58 mm |
| Depth (EF000049) | 54 mm |