View larger
DILM7-01(*V60HZ) 276598 EATON ELECTRIC Star-delta contactor combination, 132kW/400V/AC3
DILM7-01(*V60HZ)
276598
-
EATON - MOELLER
10 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller DILM7-01(*V60HZ) star-delta contactor combination is a specialized assembly designed for reduced-voltage starting of large induction motors, mitigating inrush current spikes in heavy industrial applications. Such systems protect electrical distribution networks while ensuring smooth mechanical acceleration.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 24 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Screw connection
- Operating voltage AC 50 Hz (EF008206): 24 V
- Operating voltage AC 60 Hz (EF008207): 24 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 22 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 7 A
- Rated operation power at AC-3, 400 V (EF001364): 3 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 5 A
- Rated operation power at AC-4, 400 V (EF008496): 2.2 kW
- Rated operation power NEMA (EF011960): 2.2 kW
- Modular version (EF001126): No
- Width (EF000008): 45 mm
More info
▲General specifications
UL File No.: E29096
CSA File No.: 012528
CSA Class No.: 2411-03, 3211-04
UL 60947-4-1
CSA
VDE 0660
CSA-C22.2 No. 60947-4-1-14
IEC/EN 60947-4-1
CE
UL Category Control No.: NLDX
UL
Features & Functions
General
AC-3: Normal AC induction motors: starting, switch off during running
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Ambient conditions, mechanical
5.7 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
3.4 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
3.4 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Electro Magnetic Compatibility
Terminal capacities
2 x (0.75 - 2,5) mm²
2 x (0.75 - 2.5) mm²
2 x (0.75 - 2.5) mm²
2, Terminal screw, Pozidriv screwdriver
Electrical Rating
Short-circuit rating
45 A, max. Fuse, SCCR (UL/CSA)
60 A, max. CB, SCCR (UL/CSA)
30/100 kA, Fuse, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA)
25 A, Class RK5/ 20 A Class J, max. Fuse, SCCR (UL/CSA)
25 A, Class RK5/20 A, Class J, max. Fuse, SCCR (UL/CSA)
Conventional thermal current
Switching capacity
1 A, 250 V DC, (UL/CSA)
P300, DC operated (UL/CSA)
Switching time
Magnet system
1.4 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
4.4 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Motor Rating
Communication
Contacts
Safety
400 V AC, Between the contacts, According to EN 61140
Special purpose ratings
12 A (600V 60Hz 3phase, 347V 60Hz 1phase)
42 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
0.75 HP, 200 V 60 Hz 3-ph, (UL/CSA)
3.7 A, 200 V 60 Hz 3-ph, (UL/CSA)
3.9 A, 600 V 60 Hz 3-ph, (UL/CSA)
3 HP, 600 V 60 Hz 3-ph, (UL/CSA)
2 HP, 480 V 60 Hz 3-ph, (UL/CSA)
1.5 HP, 240 V 60 Hz 3-ph, (UL/CSA)
6 A, 240 V 60 Hz 3-ph, (UL/CSA)
60 A, LRA 600 V 60 Hz 3phase; (CSA)
60 A, LRA 480 V 60 Hz 3phase; (CSA)
10 A, FLA 600 V 60 Hz 3phase; (CSA)
12 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
14 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)