Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller DILM38-01(230V50HZ,240V60HZ) is a three-pole contactor built to handle demanding motor control and power switching tasks in industrial installations. Technicians rely on these components to establish and break electrical currents safely under frequent operation cycles.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 230 V
- Rated control supply voltage AC 60 Hz (EF003979): 240 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Screw connection
- Operating voltage AC 50 Hz (EF008206): 24 V
- Operating voltage AC 60 Hz (EF008207): 24 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 45 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 38 A
- Rated operation power at AC-3, 400 V (EF001364): 18.5 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 15 A
- Rated operation power at AC-4, 400 V (EF008496): 7 kW
- Rated operation power NEMA (EF011960): 14.9 kW
- Modular version (EF001126): No
- Width (EF000008): 45 mm
More info
▲General specifications
UL 508
CSA Std. C22.2 No. 14-05
EN 60947-4-1
VDE
VDE 0660
UL 60947-4-1
UL
CE
UL Category Control No.: NLDX
CSA
CSA Class No.: 2411-03, 3211-04
CSA File No.: 012528
IEC/EN 60947
IEC/EN 60947-4-1
CSA-C22.2 No. 60947-4-1-14
UL File No.: E29096
Features & Functions
General
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-3: Normal AC induction motors: starting, switch off during running
Ambient conditions, mechanical
3.5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
6.9 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
5.3 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Electro Magnetic Compatibility
Terminal capacities
1 x (0.75 - 16) mm², Main cables
2 x (0.75 - 10) mm², Main cables
1 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 10) mm², Main cables
1 x (0.75 - 4) mm², Control circuit cables
18 - 14, Control circuit cables
M5, Terminal screw, Main cables
2, Terminal screw, Pozidriv screwdriver
3.2 Nm, Screw terminals, Main cables
Electrical Rating
Short-circuit rating
125 A, max. Fuse, SCCR (UL/CSA)
125 A, max. CB, SCCR (UL/CSA)
125/70 A, Class J, max. Fuse, SCCR (UL/CSA)
10/65 kA, CB, SCCR (UL/CSA)
10/100 kA, Fuse, SCCR (UL/CSA)
10/100 kA, Fuse, SCCR (UL/CSA)
125/125 A, Class J, max. Fuse, SCCR (UL/CSA)
50/32 A, max. CB, SCCR (UL/CSA)
Conventional thermal current
Switching capacity
1 A, 250 V DC, (UL/CSA)
A600, AC operated (UL/CSA)
Switching time
Magnet system
2.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
8.7 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Motor Rating
Communication
Contacts
Safety
440 V AC, Between coil and contacts, According to EN 61140
Special purpose ratings
40 A (600V 60Hz 3phase, 347V 60Hz 1phase)
192 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
20 HP, 600 V 60 Hz 3-ph, (UL/CSA)
7.5 HP, 240 V 60 Hz 3-ph, (UL/CSA)
20 HP, 480 V 60 Hz 3-ph, (UL/CSA)
22 A, 600 V 60 Hz 3-ph, (UL/CSA)
25.3 A, 200 V 60 Hz 3-ph, (UL/CSA)
22 A, 240 V 60 Hz 3-ph, (UL/CSA)
7.5 HP, 200 V 60 Hz 3-ph, (UL/CSA)
240 A, LRA 480 V 60 Hz 3phase; (CSA)
40 A, FLA 480 V 60 Hz 3phase; (CSA)
180 A, LRA 600 V 60 Hz 3phase; (CSA)
40 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)