View larger
DILM32-01(24V50/60HZ) 277296 Y7-277296 EATON ELECTRIC Contactor, 3p+1N/C, 15kW/400V/AC3
DILM32-01(24V50/60HZ)
277296
Y7-277296
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for efficient machine control, the Eaton Moeller DILM32-01(24V50/60HZ) contactor manages electrical loads and motor operations within automated manufacturing systems. Standard electromechanical contactors are essential for repetitive switching in industrial environments.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 24 V
- Rated control supply voltage AC 60 Hz (EF003979): 24 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Screw connection
- Operating voltage AC 50 Hz (EF008206): 24 V
- Operating voltage AC 60 Hz (EF008207): 24 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 45 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 32 A
- Rated operation power at AC-3, 400 V (EF001364): 15 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 15 A
- Rated operation power at AC-4, 400 V (EF008496): 7 kW
- Rated operation power NEMA (EF011960): 14.9 kW
- Modular version (EF001126): No
- Width (EF000008): 45 mm
More info
▲General specifications
UL
VDE 0660
CSA Class No.: 2411-03, 3211-04
UL 60947-4-1
IEC/EN 60947
CSA
CSA File No.: 012528
UL File No.: E29096
CE
IEC/EN 60947-4-1
CSA-C22.2 No. 60947-4-1-14
Features & Functions
General
10,000,000 Operations (AC operated)
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Ambient conditions, mechanical
5.3 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
3.5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Electro Magnetic Compatibility
Terminal capacities
1 x (0.75 - 16) mm², Main cables
2 x (0.75 - 10) mm², Main cables
1 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 10) mm², Main cables
1 x (0.75 - 16) mm², Main cables
18 - 14, Control circuit cables
M5, Terminal screw, Main cables
0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver
3.2 Nm, Screw terminals, Main cables
Electrical Rating
Short-circuit rating
125 A, max. Fuse, SCCR (UL/CSA)
5 kA, SCCR (UL/CSA)
10/100 kA, Fuse, SCCR (UL/CSA)
125/70 A, Class J, max. Fuse, SCCR (UL/CSA)
10/65 kA, CB, SCCR (UL/CSA)
125/125 A, Class J, max. Fuse, SCCR (UL/CSA)
50/32 A, max. CB, SCCR (UL/CSA)
10/22 kA, CB, SCCR (UL/CSA)
Conventional thermal current
Switching capacity
10 A, 600 V AC, (UL/CSA)
A600, AC operated (UL/CSA)
Switching time
Magnet system
62 VA, Dual-frequency coil in a cold state and 1.0 x Us
62 VA, Dual-frequency coil in a cold state and 1.0 x Us
2.1 W, Dual-frequency coil in a cold state and 1.0 x Us
9.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Motor Rating
Communication
Contacts
Safety
440 V AC, Between coil and contacts, According to EN 61140
Special purpose ratings
40 A (600V 60Hz 3phase, 347V 60Hz 1phase)
32 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
7.5 HP, 200 V 60 Hz 3-ph, (UL/CSA)
7.5 HP, 240 V 60 Hz 3-ph, (UL/CSA)
20 HP, 600 V 60 Hz 3-ph, (UL/CSA)
22 A, 240 V 60 Hz 3-ph, (UL/CSA)
20 HP, 480 V 60 Hz 3-ph, (UL/CSA)
27 A, 480 V 60 Hz 3-ph, (UL/CSA)
22 A, 600 V 60 Hz 3-ph, (UL/CSA)
180 A, LRA 600 V 60 Hz 3phase; (CSA)
40 A, FLA 480 V 60 Hz 3phase; (CSA)
240 A, LRA 480 V 60 Hz 3phase; (CSA)
40 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
40 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)