View larger
DILM170(RAC440) 107014 Y7-107014 EATON ELECTRIC Contactor, 3p, 90kW/400V/AC3
DILM170(RAC440)
107014
Y7-107014
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller DILM170(RAC440) is an industrial contactor engineered to switch electrical power circuits reliably in demanding machine and automation environments. Contactors of this type are widely implemented in control panels to automate the operation of heavy industrial motors, heating systems, and lighting loads through remote control signals. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 380 V
- Rated control supply voltage AC 60 Hz (EF003979): 380 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Screw connection
- Operating voltage AC 50 Hz (EF008206): 230 V
- Operating voltage AC 60 Hz (EF008207): 230 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 225 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 170 A
- Rated operation power at AC-3, 400 V (EF001364): 90 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 65 A
- Rated operation power at AC-4, 400 V (EF008496): 33 kW
- Rated operation power NEMA (EF011960): 93 kW
- Modular version (EF001126): No
- Width (EF000008): 90 mm
More info
▲General specifications
UL File No.: E29096
CSA
CE
IEC/EN 60947-4-1
UL
VDE 0660
CSA Class No.: 2411-03, 3211-04
CSA File No.: 012528
UL Category Control No.: NLDX
UL 60947-4-1
IEC/EN 60947
Features & Functions
General
AC-3: Normal AC induction motors: starting, switch off during running
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Ambient conditions, mechanical
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Electro Magnetic Compatibility
Terminal capacities
1 x (0.75 - 2.5) mm², Control circuit cables
2 x (10 - 70) mm², Main cables
2 x (0.75 - 2.5) mm², Control circuit cables
1 x (0.75 - 4) mm², Control circuit cables
18 - 14, Control circuit cables
2 x (16 - 70) mm², Main cables
M3.5, Terminal screw, Control circuit cables
5 mm AF, Hexagon socket-head spanner, Terminal screw, Main cables
0.8 x 5.5/1 x 6 mm, Terminal screw, Control circuit cables, Standard screwdriver
1.2 Nm, Screw terminals, Control circuit cables
Electrical Rating
Short-circuit rating
600 A, max. CB, SCCR (UL/CSA)
600 A, max. Fuse, SCCR (UL/CSA)
300/300 A, Class J, max. Fuse, SCCR (UL/CSA)
250 A, max. CB, SCCR (UL/CSA)
30/100 kA, Fuse, SCCR (UL/CSA)
30 kA, CB, SCCR (UL/CSA)
300/600 A, Class J, max. Fuse, SCCR (UL/CSA)
30/100 kA, Fuse, SCCR (UL/CSA)
Conventional thermal current
Switching capacity
Switching time
Magnet system
2.3 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
2.3 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Motor Rating
Communication
Contacts
Safety
690 V AC, Between coil and contacts, According to EN 61140
Special purpose ratings
160 A (480V 60Hz 3phase, 277V 60Hz 1phase)
170 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
96 A, 480 V 60 Hz 3-ph, (UL/CSA)
100 HP, 600 V 60 Hz 3-ph, (UL/CSA)
30 HP, 200 V 60 Hz 3-ph, (UL/CSA)
92 A, 200 V 60 Hz 3-ph, (UL/CSA)
40 HP, 240 V 60 Hz 3-ph, (UL/CSA)
104 A, 240 V 60 Hz 3-ph, (UL/CSA)
75 HP, 480 V 60 Hz 3-ph, (UL/CSA)
540 A, LRA 600 V 60 Hz 3phase; (CSA)
90 A, FLA 600 V 60 Hz 3phase; (CSA)
90 A, FLA 480 V 60 Hz 3phase; (CSA)
160 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
160 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)