View larger
DILM115(RDC130) 239567 Y7-239567 EATON ELECTRIC Contactor, 3p, 55kW/400V/AC3
DILM115(RDC130)
239567
Y7-239567
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller part number DILM115(RDC130) is a three-pole contactor utilized primarily for controlling industrial electric motors, heating systems, and high-current power circuits. It provides reliable remote switching capabilities in demanding manufacturing environments and automated industrial control panels. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 0 V
- Rated control supply voltage DC (EF003980): 110 V
- Voltage type for actuating (EF008242): DC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Screw connection
- Operating voltage AC 50 Hz (EF008206): 230 V
- Operating voltage AC 60 Hz (EF008207): 230 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 160 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 115 A
- Rated operation power at AC-3, 400 V (EF001364): 55 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 55 A
- Rated operation power at AC-4, 400 V (EF008496): 28 kW
- Rated operation power NEMA (EF011960): 74 kW
- Modular version (EF001126): No
- Width (EF000008): 90 mm
More info
▲General specifications
CSA File No.: 012528
UL 60947-4-1
UL Category Control No.: NLDX
VDE 0660
CSA-C22.2 No. 60947-4-1-14
CSA
IEC/EN 60947-4-1
CE
IEC/EN 60947
UL File No.: E29096
CSA Class No.: 2411-03, 3211-04
Features & Functions
General
AC-3: Normal AC induction motors: starting, switch off during running
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Ambient conditions, mechanical
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Electro Magnetic Compatibility
Terminal capacities
1 x (0.75 - 2.5) mm², Control circuit cables
2 x (10 - 70) mm², Main cables
2 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Control circuit cables
Single 8…3/0, double 8…2/0, Main cables
2 x (16 - 70) mm², Main cables
5 mm AF, Hexagon socket-head spanner, Terminal screw, Main cables
M3.5, Terminal screw, Control circuit cables
2, Terminal screw, Control circuit cables, Pozidriv screwdriver
1.2 Nm, Screw terminals, Control circuit cables
Electrical Rating
Short-circuit rating
600 A, max. Fuse, SCCR (UL/CSA)
600 A, max. CB, SCCR (UL/CSA)
300/300 A, Class J, max. Fuse, SCCR (UL/CSA)
30/100 kA, Fuse, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA)
30/100 kA, Fuse, SCCR (UL/CSA)
30 kA, CB, SCCR (UL/CSA)
350 A, max. CB, SCCR (UL/CSA)
Conventional thermal current
Switching capacity
Switching time
Magnet system
At least smoothed two-phase bridge rectifier or three-phase rectifier
110 - 130 V DC (RDC 130)
Motor Rating
Communication
Contacts
Safety
690 V AC, Between coil and contacts, According to EN 61140
Special purpose ratings
160 A (480V 60Hz 3phase, 277V 60Hz 1phase)
690 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
92 A, 200 V 60 Hz 3-ph, (UL/CSA)
96 A, 480 V 60 Hz 3-ph, (UL/CSA)
75 HP, 480 V 60 Hz 3-ph, (UL/CSA)
30 HP, 200 V 60 Hz 3-ph, (UL/CSA)
40 HP, 240 V 60 Hz 3-ph, (UL/CSA)
99 A, 600 V 60 Hz 3-ph, (UL/CSA)
104 A, 240 V 60 Hz 3-ph, (UL/CSA)
84 A, FLA 480 V 60 Hz 3phase; (CSA)
540 A, LRA 480 V 60 Hz 3phase; (CSA)
540 A, LRA 600 V 60 Hz 3phase; (CSA)
160 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
160 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)