View larger
DILM80(42V50/60HZ) 239407 Y7-239407 EATON ELECTRIC Contactor, 3p, 37kW/400V/AC3
DILM80(42V50/60HZ)
239407
Y7-239407
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller part number DILM80(42V50/60HZ) is a DILM80(42V50/60HZ) 239407 Y7-239407 EATON ELECTRIC Contactor, 3p, 37kW/400V/AC3 built to handle substantial electrical loads in automated production facilities and large machinery. Industrial switching devices ensure safe, repeatable control of heavy electrical equipment, preventing downtime in high-demand environments. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Manufacturer: Eaton Moeller
- Manufacturer part number: DILM80(42V50/60HZ)
- Catalogue code: 239407
- Catalogue title: DILM80(42V50/60HZ) 239407 Y7-239407 EATON ELECTRIC Contactor, 3p, 37kW/400V/AC3
More info
▲General specifications
IEC/EN 60947
CSA File No.: 012528
CSA
CSA Class No.: 2411-03, 3211-04
UL File No.: E29096
IEC/EN 60947-4-1
UL Category Control No.: NLDX
VDE 0660
CSA-C22.2 No. 60947-4-1-14
CE
UL
Features & Functions
General
10,000,000 Operations (AC operated)
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
AC-3: Normal AC induction motors: starting, switch off during running
Ambient conditions, mechanical
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Electro Magnetic Compatibility
Terminal capacities
1 x (10 - 70) mm², Main cables
2 x (0.75 - 2.5) mm², Control circuit cables
1 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Control circuit cables
Single 8…3/0, double 8…2/0, Main cables
2 x (16 - 50) mm², Main cables
M3.5, Terminal screw, Control circuit cables
5 mm AF, Hexagon socket-head spanner, Terminal screw, Main cables
0.8 x 5.5/1 x 6 mm, Terminal screw, Control circuit cables, Standard screwdriver
14 Nm, Screw terminals, Main cables
Electrical Rating
Short-circuit rating
600 A, max. CB, SCCR (UL/CSA)
600 A, max. Fuse, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA)
30/100 kA, Fuse, SCCR (UL/CSA)
250 A, max. CB, SCCR (UL/CSA)
300/300 A, Class J, max. Fuse, SCCR (UL/CSA)
350 A, max. CB, SCCR (UL/CSA)
30/100 kA, Fuse, SCCR (UL/CSA)
Conventional thermal current
Switching capacity
Switching time
Magnet system
328 VA, Dual-frequency coil in a cold state and 1.0 x Us
328 VA, Dual-frequency coil in a cold state and 1.0 x Us
37.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
5.8 W, Dual-frequency coil in a cold state and 1.0 x Us
Motor Rating
Communication
Contacts
Safety
690 V AC, Between coil and contacts, According to EN 61140
Special purpose ratings
100 A (480V 60Hz 3phase, 277V 60Hz 1phase)
80 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
25 HP, 240 V 60 Hz 3-ph, (UL/CSA)
60 HP, 600 V 60 Hz 3-ph, (UL/CSA)
50 HP, 480 V 60 Hz 3-ph, (UL/CSA)
65 A, 480 V 60 Hz 3-ph, (UL/CSA)
62 A, 600 V 60 Hz 3-ph, (UL/CSA)
68 A, 240 V 60 Hz 3-ph, (UL/CSA)
62.1 A, 200 V 60 Hz 3-ph, (UL/CSA)
540 A, LRA 480 V 60 Hz 3phase; (CSA)
70 A, FLA 600 V 60 Hz 3phase; (CSA)
420 A, LRA 600 V 60 Hz 3phase; (CSA)
100 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)