View larger
DILM65(RDC24) 277908 Y7-277908 EATON ELECTRIC Contactor, 3p, 30kW/400V/AC3
DILM65(RDC24)
277908
Y7-277908
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller series DILM65(RDC24) contactor is an electromechanical switching device utilized heavily in industrial settings for repeatedly establishing and interrupting high-current power circuits connected to motors and heavy loads. Industrial control panels integrate three-pole units of this type to automate manufacturing machinery safely. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product Name: Eaton Moeller® series DILM contactor
- Catalog Number: 277908
- Model Code: DILM65(RDC24)
- EAN: 4015082779085
- Product Length/Depth: 132.1 mm
- Product Height: 115 mm
- Product Width: 55 mm
- Product Weight: 1.052 kg
- Catalog Notes: Contacts according to EN 50012
- Fitted with:: Suppressor circuit in actuating electronics
- Number of poles: Three-pole
- Application: Contactors for Motors
- Connection: Screw terminals
- Frame size: FS3
More info
▲General specifications
| Product Name | Eaton Moeller® series DILM contactor |
| Catalog Number | 277908 |
| Model Code | DILM65(RDC24) |
| EAN | 4015082779085 |
| Product Length/Depth | 132.1 mm |
| Product Height | 115 mm |
| Product Width | 55 mm |
| Product Weight | 1.052 kg |
| Certifications | CSA File No.: 012528 CSA-C22.2 No. 60947-4-1-14 UL Category Control No.: NLDX CE CSA Class No.: 2411-03, 3211-04 UL File No.: E29096 IEC/EN 60947 UL 60947-4-1 VDE 0660 UL IEC/EN 60947-4-1 CSA |
| Catalog Notes | Contacts according to EN 50012 |
Features & Functions
| Fitted with: | Suppressor circuit in actuating electronics |
| Number of poles | Three-pole |
| Number of poles | Three-pole |
| Number of poles | Three-pole |
General information
| Application | Contactors for Motors |
| Connection | Screw terminals |
| Frame size | FS3 |
| Lifespan, mechanical | 10,000,000 Operations (DC operated) |
| Operating frequency | 5000 mechanical Operations/h (DC operated) |
| Overvoltage category | III |
| Pollution degree | 3 |
| Product category | Contactors |
| Protection | Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274) |
| Rated impulse withstand voltage (Uimp) | 8000 V AC |
| Resistance per pole | 1.9 mΩ |
| Suitable for | Also motors with efficiency class IE3 |
| Utilization category | AC-4: Normal AC induction motors: starting, plugging, reversing, inching AC-1: Non-inductive or slightly inductive loads, resistance furnaces AC-3: Normal AC induction motors: starting, switch off during running |
| Voltage type | DC |
Ambient conditions, mechanical
| Shock resistance | 5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
Climatic environmental conditions
| Altitude | Max. 2000 m |
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature - max | 60 °C |
| Ambient operating temperature (enclosed) - min | -25 °C |
| Ambient operating temperature (enclosed) - max | 40 °C |
| Ambient storage temperature - min | -40 °C |
| Ambient storage temperature - max | 80 °C |
| Climatic proofing | Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 |
Electro magnetic compatibility
| Emitted interference | According to EN 60947-1 |
| Interference immunity | According to EN 60947-1 |
Terminal capacities
| Terminal capacity (copper band) | 2 x (6 x 9 x 0.8) mm (Number of segments x width x thickness), Main cables |
| Terminal capacity (flexible with ferrule) | 1 x (0.75 - 2.5) mm², Control circuit cables 1 x (0.75 - 35) mm², Main cables 2 x (0.75 - 25) mm², Main cables 2 x (0.75 - 2.5) mm², Control circuit cables |
| Terminal capacity (solid) | 1 x (0.75 - 4) mm², Control circuit cables 1 x (0.75 - 16) mm², Main cables 2 x (0.75 - 2.5) mm², Control circuit cables 2 x (0.75 - 16) mm², Main cables |
| Terminal capacity (solid/stranded AWG) | Single 14 - 1, double 14 - 2, Main cables 18 - 14, Control circuit cables |
| Terminal capacity (stranded) | 2 x (16 - 35) mm², Main cables 1 x (16 - 50) mm², Main cables |
| Stripping length (main cable) | 14 mm |
| Stripping length (control circuit cable) | 10 mm |
| Screw size | M3.5, Terminal screw, Control circuit cables M6, Terminal screw, Main cables |
| Screwdriver size | 0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver 2, Terminal screw, Pozidriv screwdriver |
| Tightening torque | 3.3 Nm, Screw terminals, Main cables 1.2 Nm, Screw terminals, Control circuit cables |
Electrical rating
| Rated breaking capacity at 220/230 V | 650 A |
| Rated breaking capacity at 380/400 V | 650 A |
| Rated breaking capacity at 500 V | 650 A |
| Rated breaking capacity at 660/690 V | 370 A |
| Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V | 98 A |
| Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V | 65 A |
| Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V | 65 A |
| Rated operational current (Ie) at AC-3, 440 V | 65 A |
| Rated operational current (Ie) at AC-3, 500 V | 65 A |
| Rated operational current (Ie) at AC-3, 660 V, 690 V | 37 A |
| Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V | 25 A |
| Rated operational current (Ie) at AC-4, 440 V | 25 A |
| Rated operational current (Ie) at AC-4, 500 V | 25 A |
| Rated operational current (Ie) at AC-4, 660 V, 690 V | 20 A |
| Rated operational current (Ie) at DC-1, 60 V | 72 A |
| Rated operational current (Ie) at DC-1, 110 V | 72 A |
| Rated operational current (Ie) at DC-1, 220 V | 65 A |
| Rated making capacity up to 690 V (cos phi to IEC/EN 60947) | 910 A |
| Rated operational power at AC-3, 240 V, 50 Hz | 22 kW |
| Rated operational power at AC-3, 380/400 V, 50 Hz | 30 kW |
| Rated operational power at AC-3, 415 V, 50 Hz | 39 kW |
| Rated operational power at AC-3, 440 V, 50 Hz | 41 kW |
| Rated operational power at AC-3, 500 V, 50 Hz | 47 kW |
| Rated operational power at AC-3, 690 V, 50 Hz | 35 kW |
| Rated operational power at AC-4, 220/230 V, 50 Hz | 7 kW |
| Rated operational power at AC-4, 240 V, 50 Hz | 7.5 kW |
| Rated operational power at AC-4, 415 V, 50 Hz | 13 kW |
| Rated operational power at AC-4, 440 V, 50 Hz | 14 kW |
| Rated operational power at AC-4, 500 V, 50 Hz | 16 kW |
| Rated operational power at AC-4, 660/690 V, 50 Hz | 17 kW |
| Rated operational voltage (Ue) at AC - max | 690 V |
| Rated insulation voltage (Ui) | 690 V |
Short-circuit rating
| Short-circuit current rating (basic rating) | 10 kA, 250 A max. fuse, SCCR (UL/CSA) 10 kA, 250 A max. CB, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 480 V) | 100 kA, 150 A CLASS J max. fuse, SCCR (UL/CSA) 30 kA, 250 A max. fuse, SCCR (UL/CSA) 65 kA, 100 A max. CB, SCCR (UL/CSA) 30 kA, 250 A max. CB, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 600 V) | 100 kA, 150 A CLASS J max. fuse, SCCR (UL/CSA) 30 kA, 250 A max. fuse, SCCR (UL/CSA) 30 kA, 250 A max. CB, SCCR (UL/CSA) |
| Short-circuit protection rating (type 1 coordination) at 400 V | 250 A gG/gL |
| Short-circuit protection rating (type 1 coordination) at 690 V | 100 A gG/gL |
| Short-circuit protection rating (type 2 coordination) at 400 V | 125 A gG/gL |
| Short-circuit protection rating (type 2 coordination) at 690 V | 80 A gG/gL |
Conventional thermal current Ith
| Conventional thermal current Ith (1-pole, enclosed) | 180 A |
| Conventional thermal current Ith (3-pole, enclosed) | 72 A |
| Conventional thermal current Ith at 55°C (3-pole, open) | 83 A |
| Conventional thermal current Ith at 60°C (3-pole, open) | 80 A |
| Conventional thermal current Ith of main contacts (1-pole, open) | 200 A |
Switching capacity
| Switching capacity (main contacts, general use) | 88 A, Maximum motor rating (UL/CSA) |
Magnet system
| Arcing time | 10 ms |
| Drop-out voltage | At least smoothed two-phase bridge rectifier or three-phase rectifier 0.6 - 0.15 x UC, DC operated |
| Duty factor | 100 % |
| Pick-up voltage | 24 - 27 V DC (RDC 24) 0.7 - 1.2 V DC x Uc |
| Power consumption (pick-up) at DC | 24 W |
| Power consumption (sealing) at DC | 1 W |
| Rated control supply voltage (Us) at DC - min | 24 V |
| Rated control supply voltage (Us) at DC - max | 27 V |
| Switching time (DC operated, make contacts, closing delay) - max | 54 ms |
| Switching time (DC operated, make contacts, opening delay) - max | 24 ms |
Motor rating
| Assigned motor power at 115/120 V, 60 Hz, 1-phase | 5 HP |
| Assigned motor power at 200/208 V, 60 Hz, 3-phase | 20 HP |
| Assigned motor power at 230/240 V, 60 Hz, 1-phase | 15 HP |
| Assigned motor power at 230/240 V, 60 Hz, 3-phase | 25 HP |
| Assigned motor power at 460/480 V, 60 Hz, 3-phase | 50 HP |
| Assigned motor power at 575/600 V, 60 Hz, 3-phase | 60 HP |
Communication
| Connection to SmartWire-DT | No |
Contacts
| Number of auxiliary contacts (normally closed contacts) | 0 |
| Number of auxiliary contacts (normally open contacts) | 0 |
| Number of contacts (normally closed) as main contact | 0 |
Safety
| Safe isolation | 440 V AC, Between the contacts, According to EN 61140 440 V AC, Between coil and contacts, According to EN 61140 |
Special purpose ratings
| Special purpose rating of ballast electrical discharge lamps | 88 A (600V 60Hz 3phase, 347V 60Hz 1phase) 88 A (480V 60Hz 3phase, 277V 60Hz 1phase) |
| Special purpose rating of definite purpose rating | 65 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA) 390 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA) |
| Special purpose rating of elevator control | 10 HP, 200 V 60 Hz 3-ph, (UL/CSA) 32.2 A, 200 V 60 Hz 3-ph, (UL/CSA) 15 HP, 240 V 60 Hz 3-ph, (UL/CSA) 30 HP, 480 V 60 Hz 3-ph, (UL/CSA) 42 A, 240 V 60 Hz 3-ph, (UL/CSA) 41 A, 600 V 60 Hz 3-ph, (UL/CSA) 40 A, 480 V 60 Hz 3-ph, (UL/CSA) 40 HP, 600 V 60 Hz 3-ph, (UL/CSA) |
| Special purpose rating of resistance air heating | 88 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA) 88 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA) |
| Special purpose rating of tungsten incandescent lamps | 88 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA) 88 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA) |
Design verification
| Equipment heat dissipation, current-dependent Pvid | 17.1 W |
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 5.7 W |
| Rated operational current for specified heat dissipation (In) | 65 A |
| Static heat dissipation, non-current-dependent Pvs | 1 W |
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |