View larger
DILM50(RDC24) 277844 Y7-277844 EATON ELECTRIC Contactor, 3p, 22kW/400V/AC3
DILM50(RDC24)
277844
Y7-277844
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller part number DILM50(RDC24) is a DILM50(RDC24) 277844 Y7-277844 EATON ELECTRIC Contactor, 3p, 22kW/400V/AC3 designed to handle demanding electrical switching tasks in heavy industrial systems. These electromagnetic switches offer robust performance for driving large industrial machinery, compressors, and power distribution grids. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Manufacturer: Eaton Moeller
- Manufacturer part number: DILM50(RDC24)
- Catalogue code: 277844
- Catalogue title: DILM50(RDC24) 277844 Y7-277844 EATON ELECTRIC Contactor, 3p, 22kW/400V/AC3
More info
▲General specifications
IEC/EN 60947
VDE 0660
CSA-C22.2 No. 60947-4-1-14
UL 60947-4-1
UL
IEC/EN 60947-4-1
UL File No.: E29096
CSA File No.: 012528
UL Category Control No.: NLDX
CE
CSA
Features & Functions
General
AC-3: Normal AC induction motors: starting, switch off during running
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Ambient conditions, mechanical
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Electro Magnetic Compatibility
Terminal capacities
1 x (0.75 - 35) mm², Main cables
2 x (0.75 - 25) mm², Main cables
2 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 16) mm², Main cables
1 x (0.75 - 4) mm², Control circuit cables
Single 14 - 1, double 14 - 2, Main cables
1 x (16 - 50) mm², Main cables
M6, Terminal screw, Main cables
2, Terminal screw, Pozidriv screwdriver
3.3 Nm, Screw terminals, Main cables
Electrical Rating
Short-circuit rating
250 A, max. CB, SCCR (UL/CSA)
10 kA, SCCR (UL/CSA)
30/100 kA, Fuse, SCCR (UL/CSA)
100 A, max. CB, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA)
30 kA, CB, SCCR (UL/CSA)
250 A, max. CB, SCCR (UL/CSA)
30/100 kA, Fuse, SCCR (UL/CSA)
Conventional thermal current
Switching capacity
Switching time
Magnet system
At least smoothed two-phase bridge rectifier or three-phase rectifier
24 - 27 V DC (RDC 24)
Motor Rating
Communication
Contacts
Safety
440 V AC, Between the contacts, According to EN 61140
Special purpose ratings
79 A (600V 60Hz 3phase, 347V 60Hz 1phase)
15 HP, 240 V 60 Hz 3-ph, (UL/CSA)
42 A, 240 V 60 Hz 3-ph, (UL/CSA)
30 HP, 480 V 60 Hz 3-ph, (UL/CSA)
40 A, 480 V 60 Hz 3-ph, (UL/CSA)
10 HP, 200 V 60 Hz 3-ph, (UL/CSA)
32.2 A, 200 V 60 Hz 3-ph, (UL/CSA)
40 HP, 600 V 60 Hz 3-ph, (UL/CSA)
79 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)