View larger
DILL18(230V50HZ,240V60HZ) 104405 Y7-104405 EATON ELECTRIC Contactor, 3p, 18A, for lamp load (HQL)
DILL18(230V50HZ,240V60HZ)
104405
Y7-104405
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller Contactor DILL18(230V50HZ,240V60HZ) provides specialized switching capabilities tailored for lighting control and lamp load management. These industrial contactors are routinely installed in commercial and manufacturing facilities to regulate high-intensity discharge and fluorescent lighting networks.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Permissible compensation capacitance: Cmax [mF]
- Filament lamp: Ie [A]
- Mercury blended lamps: Ie [A]
- Fluorescent lamps, duo circuit (series compensated): Ie [A]
- electronic upstream devices and LED lamps: Ie [A]
- High-pressure mercury-arc lamps: Ie [A]
- Metal-halide lamps: Ie [A]
- Low-pressure sodium lamps: Ie [A]
- Permissible compensation capacitance: Cmax [mF]
- Filament lamp: Ie [A]
- Mercury blended lamps: Ie [A]
- Fluorescent lamps, duo circuit (series compensated): Ie [A]
- electronic upstream devices and LED lamps: Ie [A]
- High-pressure mercury-arc lamps: Ie [A]
- Metal-halide lamps: Ie [A]
- Low-pressure sodium lamps: Ie [A]
More info
▲Delivery program
| Switchgear for lighting systems | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| DIL | L12 | L18 | L20 | M7 | M9 | M12 | M17 | M25 | M32 | M40 | M50 | |
| Permissible compensation capacitance | Cmax [mF] | 470 | 470 | 470 | 47 | 80 | 100 | 220 | 330 | 470 | 470 | 500 |
| Filament lamp | Ie [A] | 14 | 21 | 27 | 6 | 7.5 | 10 | 14 | 21 | 27 | 33 | 42 |
| Mercury blended lamps | Ie [A] | 12 | 16 | 23 | 5 | 6.5 | 8.5 | 12 | 16 | 23 | 30 | 38 |
| Fluorescent lamps, conventional -reactor – starter – connection | Ie [A] | 20 | 26 | 35 | 9 | 10 | 15 | 20 | 26 | 35 | 41 | 45 |
| Fluorescent lamps, conventional -reactor – starter – connection | Ie [A] | 20 | 26 | 35 | 5.5 | 8 | 13 | 15 | 22.5 | 29 | 36 | 47 |
| Fluorescent lamps, duo circuit (series compensated) | Ie [A] | 12 | 18 | 20 | 5 | 6.5 | 8.5 | 12 | 17.5 | 22.5 | 28 | 35 |
| electronic upstream devices and LED lamps | Ie [A] | 12 | 18 | 20 | 3.5 | 6 | 10 | 12 | 17.5 | 20 | 25 | 30 |
| High-pressure mercury-arc lamps | Ie [A] | 12 | 18 | 20 | 3.5 | 6 | 10 | 12 | 17.5 | 20 | 25 | 30 |
| Metal-halide lamps | Ie [A] | 12 | 18 | 20 | 3.5 | 6 | 10 | 12 | 17.5 | 20 | 25 | 30 |
| Low-pressure sodium lamps | Ie [A] | 7.5 | 10 | 12 | 3 | 4 | 6 | 7.5 | 10 | 12 | 15 | 22 |
| DIL | M65 | M80 | M95 | M115 | M150 | M185A | M225A | M250A | M300A | M400A | M500A | |
| Permissible compensation capacitance | Cmax [mF] | 500 | 550 | 620 | 830 | 970 | 2055 | 2300 | 2600 | 3000 | 3250 | 3500 |
| Filament lamp | Ie [A] | 55 | 67 | 79 | 95 | 125 | 153 | 187 | 208 | 349 | 332 | 415 |
| Mercury blended lamps | Ie [A] | 45 | 65 | 67 | 80 | 110 | 123 | 150 | 167 | 200 | 266 | 332 |
| Fluorescent lamps, conventional -reactor – starter – connection | Ie [A] | 55 | 95 | 100 | 125 | 145 | 207 | 237 | 263 | 300 | 375 | 525 |
| Fluorescent lamps, conventional -reactor – starter – connection | Ie [A] | 59 | 71 | 95 | 100 | 138 | 186 | 213 | 236 | 270 | 338 | 473 |
| Fluorescent lamps, duo circuit (series compensated) | Ie [A] | 45.5 | 56 | 66.5 | 80.5 | 105 | 130 | 158 | 175 | 210 | 280 | 350 |
| electronic upstream devices and LED lamps | Ie [A] | 36 | 55 | 60 | 80 | 95 | 138 | 158 | 175 | 200 | 250 | 350 |
| High-pressure mercury-arc lamps | Ie [A] | 36 | 55 | 60 | 80 | 95 | 138 | 158 | 175 | 200 | 250 | 350 |
| Metal-halide lamps | Ie [A] | 36 | 55 | 60 | 80 | 95 | 138 | 158 | 175 | 200 | 250 | 350 |
| Low-pressure sodium lamps | Ie [A] | 25 | 35 | 40 | 50 | 70 | 100 | 11 | 123 | 140 | 175 | 245 |
| In compensated lamps, the sum of the capacitances must not exceed the contactors' max. permissible capacitor load (Cmax)! The values in the table are for each contact in the contactors. | ||||||||||||
Technical data
Damp heat, cyclic, to IEC 60068-2-30