View larger
DILM40(48V50HZ) 277754 Y7-277754 EATON ELECTRIC Contactor, 3p, 18.5kW/400V/AC3
DILM40(48V50HZ)
277754
Y7-277754
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller contactor (DILM40(48V50HZ)) serves as a high-performance electrical switch for heavy-duty motor control and industrial power automation. It provides reliable operational switching in centralized electrical enclosures.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz: 48 V
- Rated control supply voltage AC 60 Hz: 0 V
- Rated control supply voltage DC: 0 V
- Voltage type for actuating: AC
- Number of normally open contacts as main contact: 3
- Type of electrical connection of main circuit: Screw connection
- Operating voltage AC 50 Hz: 230 V
- Operating voltage AC 60 Hz: 230 V
- Rated operation current Ie at AC-1, 400 V: 60 A
- Rated operation current Ie at AC-3, 400 V: 40 A
- Rated operation power at AC-3, 400 V: 18.5 kW
- Rated operation current Ie at AC-4, 400 V: 18 A
- Rated operation power at AC-4, 400 V: 9 kW
- Rated operation power NEMA: 22 kW
- Modular version: No
- Width: 55 mm
More info
▲General specifications
IEC 60947-4-1
CSA Std. C22.2 No. 14-05
EN 60947-4-1
VDE
CSA File No.: 012528
IEC/EN 60947-4-1
UL Category Control No.: NLDX
CE
CSA-C22.2 No. 14-05
UL File No.: E29096
IEC/EN 60947
VDE 0660
UL
CSA Class No.: 2411-03, 3211-04
CSA
Features & Functions
General
AC-3: Normal AC induction motors: starting, switch off during running
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Ambient conditions, mechanical
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Electro Magnetic Compatibility
Terminal capacities
2 x (0.75 - 25) mm², Main cables
1 x (0.75 - 2.5) mm², Control circuit cables
1 x (0.75 - 35) mm², Main cables
2 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 16) mm², Main cables
1 x (0.75 - 4) mm², Control circuit cables
18 - 14, Control circuit cables
2 x (16 - 35) mm², Main cables
M6, Terminal screw, Main cables
2, Terminal screw, Pozidriv screwdriver
1.2 Nm, Screw terminals, Control circuit cables
Electrical Rating
Short-circuit rating
250 A, max. CB, SCCR (UL/CSA)
250 A, max. Fuse, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA)
30/100 kA, Fuse, SCCR (UL/CSA)
250/150 A, Class J, max. Fuse, SCCR (UL/CSA)
30/100 kA, Fuse, SCCR (UL/CSA)
30 kA, CB, SCCR (UL/CSA)
250/150 A, Class J, max. Fuse, SCCR (UL/CSA)
Conventional thermal current
Switching capacity
Switching time
Magnet system
4.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
4.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Motor Rating
Communication
Contacts
Safety
440 V AC, Between the contacts, According to EN 61140
Special purpose ratings
79 A (480V 60Hz 3phase, 277V 60Hz 1phase)
32 A, 600 V 60 Hz 3-ph, (UL/CSA)
34 A, 480 V 60 Hz 3-ph, (UL/CSA)
30 HP, 600 V 60 Hz 3-ph, (UL/CSA)
25.3 A, 200 V 60 Hz 3-ph, (UL/CSA)
28 A, 240 V 60 Hz 3-ph, (UL/CSA)
7.5 HP, 200 V 60 Hz 3-ph, (UL/CSA)
25 HP, 480 V 60 Hz 3-ph, (UL/CSA)
79 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
74 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)