View larger
M22-KC10 216380 Y7-216380 EATON ELECTRIC Contact element, 1N/O, base fixing, 6. contact, screw connection
M22-KC10
M22-KC10
Y7-216380
EATON - MOELLER
1 unit
Automation > Auxiliary contact block
Auxiliary Control and Signalling Elements
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A contact element, such as the Eaton Moeller M22-KC10, is a modular electrical switching block used extensively in control and signaling devices like pushbuttons and selector switches. When mechanical pressure is applied to the front actuator, the internal mechanism changes state to interrupt or complete a control circuit path. These elements are widely deployed in industrial control panels for machine operation and safety interlocks.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of contacts as change-over contact: 0
- Number of contacts as normally open contact: 1
- Number of contacts as normally closed contact: 0
- Number of fault-signal switches: 0
- Rated operation current Ie at AC-15, 230 V: 6 A
- Type of electric connection: Screw connection
- Model: Clip-on
- Mounting method: Floor fastening
More info
▲General specifications
| Product Name | Eaton Moeller® series M22 Accessory Contact element |
| Catalog Number | 216380 |
| Model Code | M22-KC10 |
| EAN | 4015082163808 |
| Product Length/Depth | 38 mm |
| Product Height | 10 mm |
| Product Width | 32 mm |
| Product Weight | 0.01 kg |
| Compliances | CE Marked |
| Certifications | EN 60947-5 UL 508 CSA Std. C22.2 No. 14-05 IEC 60947-5 CSA Std. C22.2 No. 94-91 VDE IEC/EN 60947-5 UL Category Control No.: NKCR CSA UL CSA Class No.: 3211-03 CSA File No.: 012528 UL File No.: E29184 CSA-C22.2 No. 14-05 CE CSA-C22.2 No. 94-91 IEC 60947-5-1 |
Features & Functions
| Color | Green |
| Electric connection type | Screw connection |
General information
| Degree of protection | IP20 |
| Lifespan, electrical | 1,200,000 Operations (at 12 V, DC-13, 2.8 A) 1,000,000 Operations (at 230 V, AC-15, 1 A) 1,600,000 Operations (at 230 V, 0.5 A) 700,000 Operations (at 230 V, AC-15, 3 A) |
| Lifespan, mechanical | 5,000,000 Operations |
| Model | Top mounting |
| Mounting method | Floor fastening |
| Operating frequency | 3600 Operations/h |
| Operating torque | 0.8 Nm |
| Overvoltage category | III |
| Pollution degree | 3 |
| Rated impulse withstand voltage (Uimp) | 6000 V AC |
Ambient conditions, mechanical
| Shock resistance | 30 g, Mechanical, According to IEC/EN 60068-2-27, Sinusoidal shock 11 ms |
Climatic environmental conditions
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature - max | 70 °C |
| Ambient storage temperature - min | -25 °C |
| Ambient storage temperature - max | 85 °C |
| Climatic proofing | Damp heat, cyclic, to IEC 60068-2-30 Damp heat, constant, to IEC 60068-2-78 |
Terminal capacities
| Terminal capacity (flexible with ferrule) | 0.5 - 1.5 mm² |
| Terminal capacity (solid) | 0.75 - 2.5 mm² |
| Terminal capacity (stranded) | 0.5 - 2.5 mm² |
Electrical rating
| Rated insulation voltage (Ui) | 500 V |
| Rated operational current (Ie) at AC-15, 115 V | 6 A |
| Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V | 6 A |
| Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V | 4 A |
| Rated operational current (Ie) at AC-15, 500 V | 2 A |
| Rated operational current (Ie) at DC-13, 24 V | 3 A |
| Rated operational current (Ie) at DC-13, 42 V | 1.7 A |
| Rated operational current (Ie) at DC-13, 60 V | 1.2 A |
| Rated operational current (Ie) at DC-13, 110 V | 0.6 A |
| Rated operational current (Ie) at DC-13, 220 V, 230 V | 0.3 A |
| Rated operational current (Ie) at DC-13, 500 V | 0.1 A |
Short-circuit rating
| Short-circuit protection | PKZM0-10/FAZ-B6/1, Contacts, Max. short-circuit protective device, Fuseless |
| Short-circuit protection rating | Max. 10 A gG/gL, Fuse, Contacts |
Communication
| Connection to SmartWire-DT | No |
| Connection type | Base fixing Single contact Screw connection |
Actuator
| Actuating force - max | 5 N |
Contacts
| Control circuit reliability | 1 failure per 5,000,000 switching operations (statistically determined, at 5 V DC/1 mA) 1 failure per 10,000,000 switching operations (Statistically determined, at 24 V DC/5 mA) |
| Force for positive opening - min | 0 N |
| Number of contacts (change-over contacts) | 0 |
| Number of contacts (normally closed contacts) | 0 |
| Number of contacts (normally open contacts) | 1 |
Design verification
| Equipment heat dissipation, current-dependent Pvid | 0 W |
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 0.11 W |
| Rated operational current for specified heat dissipation (In) | 6 A |
| Static heat dissipation, non-current-dependent Pvs | 0 W |
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |