View larger
BP-U-600/7-C-W 105937 EATON ELECTRIC Complete flush-mounting service distribution board with three-point tur..
BP-U-600/7-C-W
105937
EATON - MOELLER
1 Pcs.
Automation > Small distribution board
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Distributed by Eaton Moeller, the BP-U-600/7-C-W 105937 EATON ELECTRIC Complete flush-mounting service distribution board with three-point tur.. functions as an integrated enclosure system for flush-wall installation of power distribution equipment. Flush-mounted enclosures provide a clean, space-saving profile while securely housing modular switching gear and terminal connections within structural walls.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Individual enclosure, flush mounting: P V
- Individual enclosure, flush mounting: P V
- Mounting method (EF000003): Flush mounted
- Number of rows (EF000266): 4
- Width in number of modular spacings (EF002950): 24
- Transparent cover/door (EF006244): No
- Signal passing door (EF015941): No
- With lock (EF006306): No
- Housing material (EF001596): Steel
- Built-in depth (EF000218): 240 mm
- Earthing terminal block (EF015776): No
- Neutral terminal block (EF015777): No
- DIN-rail (EF001134): Yes With mounting plate (EF000118): No
- Extension possible (EF001088): Yes
- EMC-version (EF001062): No
More info
▲Technical data for design verification | |||
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees, calculated as per IEC 60890 | |||
Individual enclosure, flush mounting | PV | CO | 52 |
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees, calculated as per IEC 60890 | |||
Individual enclosure, flush mounting | PV | CO | 105 |
IEC/EN 61439 design verification | |||
10.2 Strength of materials and parts | |||
10.2.2 Corrosion resistance | Meets the product standard's requirements. | ||
10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. | ||
10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. | ||
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects | Meets the product standard's requirements. | ||
10.2.4 Resistance to ultra-violet (UV) radiation | Not relevant to indoor installations. | ||
10.2.5 Lifting | Does not apply to enclosures without lifting aids. | ||
10.2.6 Mechanical impact | IK07 | ||
10.2.7 Inscriptions | Meets the product standard's requirements. | ||
10.3 Degree of protection of ASSEMBLIES | IP30 | ||
10.4 Clearances and creepage distances | Is the panel builder's responsibility. | ||
10.5 Protection against electric shock | < 0.1 Ω; meets the product standard's requirements. | ||
10.6 Incorporation of switching devices and components | Is the panel builder's responsibility. | ||
10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. | ||
10.8 Connections for external conductors | Is the panel builder's responsibility. | ||
10.9 Insulation properties | |||
10.9.2 Power-frequency electric strength | Ui= 440 V AC | ||
10.9.3 Impulse withstand voltage | 4 kV | ||
10.9.4 Testing of enclosures made of insulating material | Does not apply to metal enclosures. | ||
10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. | ||
10.11 Short-circuit rating | Is the panel builder's responsibility. | ||
10.12 Electromagnetic compatibility | Is the panel builder's responsibility. | ||
10.13 Mechanical function | Meets the product standard's requirements. |
| Distribution boards (EG000023) / Small distribution board (EC000214) | |||
| Electric engineering, automation, process control engineering / Electrical installation, device / Electrical distribution system (incl. small distribution board) / Small distribution board (ecl@ss8-27-14-24-09 [ACN387007]) | |||
Mounting method | Flush mounted (plaster) | ||
Number of rows | 4 | ||
Width in number of modular spacings | 24 | ||
Type of cover | Closed | ||
With transparent cover | No | ||
Material housing | Steel | ||
Height | mm | 700 | |
Width | mm | 600 | |
Depth | mm | 247 | |
Built-in depth | mm | 240 | |
DIN-rail | Yes | ||
With mounting plate | No | ||
Extension possible | Yes | ||
EMC-version | No | ||
Colour | White | ||
RAL-number | 9016 | ||
Degree of protection (IP) | IP30 | ||