View larger
LZMC3-4-A500/320-I 111962 Y7-111962 EATON ELECTRIC Circuit-breaker, 4 p, 500A, 230A, in 4th pole
LZMC3-4-A500/320-I
111962
Y7-111962
EATON - MOELLER
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Circuit Breakers LZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller LZMC3-4-A500/320-I circuit-breaker acts as a critical safety device designed to automatically disconnect electrical circuits during fault conditions, protecting equipment from severe damage. Four-pole configurations of this type are frequently deployed in complex commercial and industrial power systems requiring neutral conductor switching and comprehensive thermal-magnetic protection.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated permanent current Iu (EF001389): 500 A
- Rated voltage (EF003977): 690 V
- Overload release current setting (EF002336): 400 A
- Adjustment range undelayed short-circuit release (EF007131): 3000 A
- Device construction (EF008240): Built-in device fixed built-in technique
- Integrated earth fault protection (EF007296): No
- Type of electrical connection of main circuit (EF006819): Screw connection
- Suitable for DIN rail (top hat rail) mounting (EF007250): No
- DIN rail (top hat rail) mounting optional (EF008904): No
- With switched-off indicator (EF007006): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 4
- Position of connection for main current circuit (EF006671): Front
- Type of control element (EF006976): Rocker lever
- Complete device with protection unit (EF008906): Yes
- Motor drive integrated (EF006697): No
More info
▲General specifications
IEC
IEC/EN 60947
Delivery program
Technical data - electrical
500 A (690 V AC -1, making and breaking capacity)
450 A (660-690 V AC-3, making and breaking capacity)
500 A (415 V AC-1, making and breaking capacity)
450 A (415 V AC-3, making and breaking capacity)
500 V AC (between auxiliary contacts and main contacts)
2000 operations at 690 V AC-3
5000 operations at 400 V AC-1
2000 operations at 400 V AC-3
Technical data - mechanical
Fixed
IP20
IP66 (with door coupling rotary handle)
IP00 (terminations, phase isolator and band terminal)
Damp heat, cyclic, to IEC 60068-2-30
Design verification as per IEC/EN 61439 - technical data
Design verification as per IEC/EN 61439
Additional information
Motor drive optional