EATON - MOELLER LZMC2-4-VE160-I LZMC2-4-VE160-I 116481 Y7-116481 EATON ELECTRIC Circuit-breaker, 4 p, 160A View larger
Images are for illustrative purposes only. Please refer to data sheet for details

LZMC2-4-VE160-I 116481 Y7-116481 EATON ELECTRIC Circuit-breaker, 4 p, 160A

LZMC2-4-VE160-I

116481

Y7-116481

EATON - MOELLER

1 Pcs.

Circuit-breaker, 4 p, 160A LZMC2-4-VE160-I

Automation > Power circuit-breaker for trafo/generator/installation protection
Circuit Breakers LZM

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

A circuit-breaker like the Eaton Moeller LZMC2-4-VE160-I 116481 Y7-116481 EATON ELECTRIC provides essential fault isolation and manual switching capabilities within industrial power distribution architectures. Devices of this type automatically interrupt electrical currents during overload or short-circuit events to protect downstream assets.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Rated permanent current Iu (EF001389): 160 A
  • Rated voltage (EF003977): 690 V
  • Overload release current setting (EF002336): 80 A
  • Adjustment range undelayed short-circuit release (EF007131): 1920 A
  • Power loss (EF005387): None W
  • Device construction (EF008240): Built-in device fixed built-in technique
  • Integrated earth fault protection (EF007296): false
  • Type of electrical connection of main circuit (EF006819): Screw connection
  • Suitable for DIN rail (top hat rail) mounting (EF007250): false
  • DIN rail (top hat rail) mounting optional (EF008904): true
  • With switched-off indicator (EF007006): false
  • With integrated under voltage release (EF001390): false
  • Number of poles (EF001391): 4
  • Position of connection for main current circuit (EF006671): Front side
  • Type of control element (EF006976): Rocker lever
  • Complete device with protection unit (EF008906): true

More info

Technical data ETIM 6.0
Low-voltage industrial components (EG000017) / Power circuit-breaker for trafo/generator/installation prot. (EC000228)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Circuit breaker for power transformer, generator and system protection ([email protected] [AJZ716010])
Rated permanent current Iu
A 160
Rated voltage
V 690 - 690
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
kA 36
Overload release current setting
A 80 - 160
Adjustment range short-term delayed short-circuit release
A 160 - 1600
Adjustment range undelayed short-circuit release
A 1920 - 1920
Integrated earth fault protection
No
Type of electrical connection of main circuit
Screw connection
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
Yes
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Switched-off indicator available
No
With under voltage release
No
Number of poles
4
Position of connection for main current circuit
Front side
Type of control element
Rocker lever
Complete device with protection unit
Yes
Motor drive integrated
No
Motor drive optional
Yes
Degree of protection (IP)
IP20

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.