Eaton Moeller LZMC1-A32-I is a three-pole circuit breaker used in electrical panels to protect wiring and connected loads from overcurrent damage. Circuit breakers of this rating isolate faulty branches safely during short circuits or sustained thermal overloads. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated permanent current Iu (EF001389): 32 A
- Rated voltage (EF003977): 690 V
- Overload release current setting (EF002336): 25 A
- Adjustment range undelayed short-circuit release (EF007131): 350 A
- Device construction (EF008240): Built-in device fixed built-in technique
- Integrated earth fault protection (EF007296): No
- Type of electrical connection of main circuit (EF006819): Frame clamp
- Suitable for DIN rail (top hat rail) mounting (EF007250): No
- DIN rail (top hat rail) mounting optional (EF008904): Yes
- With switched-off indicator (EF007006): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
- Position of connection for main current circuit (EF006671): Front
- Type of control element (EF006976): Rocker lever
- Complete device with protection unit (EF008906): Yes
- Motor drive integrated (EF006697): No
More info
▲General specifications
IEC/EN 60947
IEC
Delivery program
Technical data - electrical
160 A (690 V AC-1, making and breaking capacity)
125 A (415 V AC-1, making and breaking capacity)
32 A (415 V AC-3, making and breaking capacity)
32 A (660-690 V AC-3, making and breaking capacity)
300 V AC (between the auxiliary contacts)
7500 operations at 690 V AC-1
10000 operations at 415 V AC-1
7500 operations at 415 V AC-3
Technical data - mechanical
Fixed
DIN rail (top hat rail) mounting optional
IP20
IP66 (with door coupling rotary handle)
IP00 (terminations, phase isolator and band terminal)
0.75 mm² - 1.5 mm² (2x)
Min. 12 mm x 5 mm direct at switch rear-side connection
M8 at rear-side screw connection
10 mm² - 16 mm² (1x) direct at switch rear-side connection
6 mm² - 16 mm² (2x) direct at switch rear-side connection
6 mm² - 16 mm² (2x) at box terminal
16 mm² - 95 mm² (1x) at tunnel terminal
25 mm² - 70 mm² (1x) at box terminal
25 mm² (2x) at box terminal
25 mm² - 95 mm² (1x) at tunnel terminal
25 mm² (2x) direct at switch rear-side connection
Max. 9 segments of 9 mm x 0.8 mm at box terminal
Damp heat, constant, to IEC 60068-2-78