LZMB2-A300-I 111925 Y7-111925 EATON ELECTRIC Circuit-breaker, 3 p, 300A
LZMB2-A300-I
111925
Y7-111925
EATON - MOELLER
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Circuit Breakers LZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller circuit-breaker (LZMB2-A300-I) serves as a protective switching device intended to guard electrical circuits against damage caused by excess current from overloads or short circuits. These components are commonly installed within industrial machinery and power distribution assemblies to safely interrupt fault currents and manually disconnect power supplies when required.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated permanent current Iu (EF001389): 300 A
- Rated voltage (EF003977): 440 V
- Overload release current setting (EF002336): 240 A
- Adjustment range undelayed short-circuit release (EF007131): 2000 A
- Power loss (EF005387): None W
- Device construction (EF008240): Built-in device fixed built-in technique
- Integrated earth fault protection (EF007296): false
- Type of electrical connection of main circuit (EF006819): Screw connection
- Suitable for DIN rail (top hat rail) mounting (EF007250): false
- DIN rail (top hat rail) mounting optional (EF008904): true
- With switched-off indicator (EF007006): false
- With integrated under voltage release (EF001390): false
- Number of poles (EF001391): 3
- Position of connection for main current circuit (EF006671): Front side
- Type of control element (EF006976): Rocker lever
- Complete device with protection unit (EF008906): true
More info
▲General specifications
IEC
VDE 0660
Delivery program
Technical data - electrical
300 A (380/400 V AC-1, making and breaking capacity)
300 A (415 V AC-1, making and breaking capacity)
300 A (415 V AC-3, making and breaking capacity)
500 V AC (between auxiliary contacts and main contacts)
10000 operations at 415 V AC-1
10000 operations at 400 V AC-1
Technical data - mechanical
Fixed
DIN rail (top hat rail) mounting optional
In the area of the HMI devices: IP20 (basic protection type)
IP66 (with door coupling rotary handle)
IP10 (tunnel terminal)
0.75 mm² - 2.5 mm² (1x)
Min. 16 mm x 5 mm direct at switch rear-side connection
M8 at rear-side screw connection
4 mm² - 16 mm² (2x) at box terminal
16 mm² (1x) at tunnel terminal
4 mm² - 16 mm² (1x) at box terminal
4 mm² - 16 mm² (2x) direct at switch rear-side connection
25 mm² - 185 mm² (1x) direct at switch rear-side connection
25 mm² - 70 mm² (2x) at box terminal
25 mm² - 70 mm² (2x) direct at switch rear-side connection
25 mm² - 185 mm² (1x) at box terminal
Min. 2 segments of 9 mm x 0.8 mm at box terminal
Max. 10 segments of 16 mm x 0.8 mm at rear-side connection (punched)
Min. 2 segements of 16 mm x 0.8 mm at rear-side connection (punched)
Damp heat, constant, to IEC 60068-2-78
Design verification as per IEC/EN 61439 - technical data
Design verification as per IEC/EN 61439
Additional information
Motor drive optional