Eaton Moeller LZMB1-A40-I is a compact 3-pole molded case circuit breaker engineered to protect low-voltage electrical circuits against overloads and short circuits. Control panel builders integrate this device type into commercial distribution boards to ensure dependable branch protection. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated permanent current Iu (EF001389): 40 A
- Rated voltage (EF003977): 440 V
- Overload release current setting (EF002336): 32 A
- Adjustment range undelayed short-circuit release (EF007131): 320 A
- Device construction (EF008240): Built-in device fixed built-in technique
- Integrated earth fault protection (EF007296): No
- Type of electrical connection of main circuit (EF006819): Frame clamp
- Suitable for DIN rail (top hat rail) mounting (EF007250): No
- DIN rail (top hat rail) mounting optional (EF008904): Yes
- With switched-off indicator (EF007006): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
- Position of connection for main current circuit (EF006671): Front
- Type of control element (EF006976): Rocker lever
- Complete device with protection unit (EF008906): Yes
- Motor drive integrated (EF006697): No
More info
▲General specifications
IEC/EN 60947
VDE 0660
Delivery program
Technical data - electrical
40 A (660-690 V AC-3, making and breaking capacity)
40 A (415 V AC-3, making and breaking capacity)
125 A (415 V AC-1, making and breaking capacity)
500 V AC (between auxiliary contacts and main contacts)
7500 operations at 400 V AC-1
7500 operations at 415 V AC-3
Technical data - mechanical
Fixed
DIN rail (top hat rail) mounting optional
In the area of the HMI devices: IP20 (basic protection type)
IP40 (with insulating surround)
IP10 (tunnel terminal)
0.75 mm² - 1.5 mm² (2x)
Max. 16 mm x 5 mm direct at switch rear-side connection
M8 at rear-side screw connection
10 mm² - 16 mm² (1x) direct at switch rear-side connection
6 mm² - 16 mm² (2x) direct at switch rear-side connection
6 mm² - 16 mm² (2x) at box terminal
16 mm² - 95 mm² (1x) at tunnel terminal
25 mm² (2x) direct at switch rear-side connection
25 mm² - 95 mm² (1x) at tunnel terminal
25 mm² - 70 mm² (1x) at box terminal
25 mm² - 70 mm² (1x) direct at switch rear-side connection
Min. 2 segments of 9 mm x 0.8 mm at box terminal
Damp heat, constant, to IEC 60068-2-78