View larger
LZMB1-4-ASF50-I 111862 Y7-111862 EATON ELECTRIC Circuit-breaker, 4 p, 50A
LZMB1-4-ASF50-I
111862
Y7-111862
EATON - MOELLER
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Circuit Breakers LZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller LZMB1-4-ASF50-I is a 4-pole circuit breaker configured to protect electrical distribution lines and connected machinery from overloads. Compact circuit breakers are widely used in commercial buildings and industrial control cabinets for reliable branch circuit protection.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Rated permanent current Iu (EF001389): 50 A
- Rated voltage (EF003977): 690 V
- Overload release current setting (EF002336): 40 A
- Adjustment range undelayed short-circuit release (EF007131): 300 A
- Power loss (EF005387): None W
- Device construction (EF008240): Built-in device fixed built-in technique
- Integrated earth fault protection (EF007296): false
- Type of electrical connection of main circuit (EF006819): Frame clamp
- Suitable for DIN rail (top hat rail) mounting (EF007250): false
- DIN rail (top hat rail) mounting optional (EF008904): true
- With switched-off indicator (EF007006): false
- With integrated under voltage release (EF001390): false
- Number of poles (EF001391): 4
- Position of connection for main current circuit (EF006671): Front side
- Type of control element (EF006976): Rocker lever
- Complete device with protection unit (EF008906): true
More info
▲| Low-voltage industrial components (EG000017) / Power circuit-breaker for trafo/generator/installation prot. (EC000228) | |||
| Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Circuit breaker for power transformer, generator and system protection ([email protected] [AJZ716010]) | |||
Rated permanent current Iu | A | 50 | |
Rated voltage | V | 690 - 690 | |
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz | kA | 25 | |
Overload release current setting | A | 40 - 50 | |
Adjustment range short-term delayed short-circuit release | A | 0 - 0 | |
Adjustment range undelayed short-circuit release | A | 300 - 500 | |
Integrated earth fault protection | No | ||
Type of electrical connection of main circuit | Frame clamp | ||
Device construction | Built-in device fixed built-in technique | ||
Suitable for DIN rail (top hat rail) mounting | No | ||
DIN rail (top hat rail) mounting optional | Yes | ||
Number of auxiliary contacts as normally closed contact | 0 | ||
Number of auxiliary contacts as normally open contact | 0 | ||
Number of auxiliary contacts as change-over contact | 0 | ||
Switched-off indicator available | No | ||
With under voltage release | No | ||
Number of poles | 4 | ||
Position of connection for main current circuit | Front side | ||
Type of control element | Rocker lever | ||
Complete device with protection unit | Yes | ||
Motor drive integrated | No | ||
Motor drive optional | No | ||
Degree of protection (IP) | IP20 | ||