View larger
LZMB1-4-A40-I 111871 Y7-111871 EATON ELECTRIC Circuit-breaker, 4 p, 40A
LZMB1-4-A40-I
111871
Y7-111871
EATON - MOELLER
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Circuit Breakers LZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A circuit-breaker, identified as the LZMB1-4-A40-I 111871 Y7-111871 EATON ELECTRIC Circuit-breaker, 4 p, 40A from Eaton Moeller, provides dependable automated protection for low-voltage power distribution systems by interrupting current flow during overload or short-circuit conditions. These modular switching devices protect machinery, wiring, and infrastructure from electrical damage across industrial plants.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated permanent current Iu (EF001389): 40 A
- Rated voltage (EF003977): 440 V
- Overload release current setting (EF002336): 32 A
- Adjustment range undelayed short-circuit release (EF007131): 320 A
- Power loss (EF005387): None W
- Device construction (EF008240): Built-in device fixed built-in technique
- Integrated earth fault protection (EF007296): false
- Type of electrical connection of main circuit (EF006819): Frame clamp
- Suitable for DIN rail (top hat rail) mounting (EF007250): false
- DIN rail (top hat rail) mounting optional (EF008904): true
- With switched-off indicator (EF007006): false
- With integrated under voltage release (EF001390): false
- Number of poles (EF001391): 4
- Position of connection for main current circuit (EF006671): Front side
- Type of control element (EF006976): Rocker lever
- Complete device with protection unit (EF008906): true
More info
▲General specifications
VDE 0660
IEC
Product specifications
DIN rail (top hat rail) mounting optional
Fixed
Damp heat, cyclic, to IEC 60068-2-30
300 V AC (between the auxiliary contacts)
In the area of the HMI devices: IP20 (basic protection type)
125 A (415 V AC-1, making and breaking capacity)
160 A (380/400 V AC-1, making and breaking capacity)
40 A (415 V AC-3, making and breaking capacity)
IP66 (with door coupling rotary handle)
IP00 (terminations, phase isolator and band terminal)
Min. 2 segments of 9 mm x 0.8 mm at box terminal
10000 operations at 415 V AC-1
7500 operations at 415 V AC-3
0.75 mm² - 1.5 mm² (2x)
Max. 16 mm x 5 mm direct at switch rear-side connection
Min. 12 mm x 5 mm direct at switch rear-side connection
16 mm² - 95 mm² (1x) at tunnel terminal
10 mm² - 16 mm² (1x) at box terminal
10 mm² - 16 mm² (1x) direct at switch rear-side connection
6 mm² - 16 mm² (2x) direct at switch rear-side connection
25 mm² (2x) direct at switch rear-side connection
25 mm² (2x) at box terminal
25 mm² - 70 mm² (1x) direct at switch rear-side connection
25 mm² - 70 mm² (1x) at box terminal